Three Core 26/35KV Medium Voltage Unarmored Cable

26/35kV XLPE Insulated Copper Tape Screened Three Core Unarmoured Power Cable

Voltage: 26/35kV (Um=42kV)
Conductor: Copper or aluminum, compacted circular Class 2
Conductor Screen: Extruded semi-conductive compound (per core)
Insulation: XLPE, 10.5mm per core
Insulation Screen: Extruded semi-conductive compound + Cu tape screen
Assembly: 3 screened cores + filler + binder tape
Outer Sheath: PVC Type ST2, PE, or LSZH (BS 7835)

Product Overview

Three Core 26/35kV (Um=42kV) Medium Voltage Unarmoured Cable is the highest-rated three-core XLPE insulated power cable in the commercial MV/HV product range. At 10.5mm of insulation per core — the thickest of any three-core unarmoured cable — it is engineered for 35kV distribution systems where the neutral earthing method subjects healthy phases to elevated phase-to-ground voltage during earth faults. In resistance-earthed or unearthed (isolated) neutral systems, a single-phase earth fault causes the two healthy phases to rise to full phase-to-phase voltage (35kV). The 26kV U₀ rating provides the necessary 24% safety margin over the 21kV class to handle this condition without accelerated insulation ageing — a critical consideration in industrial MV networks and generator auxiliary systems where continuous operation during a single earth fault is required by operational policy.

21/35kV vs 26/35kV: U₀ Matters for System Earthing

Both 21/35kV and 26/35kV cables are rated for the same phase-to-phase voltage (35kV) — the difference is in the U₀ rating: phase-to-ground voltage. In a solidly-earthed system, a phase-to-ground fault pulls the faulted phase voltage to near zero while healthy phases remain at U₀. In a resistance-earthed or isolated system, healthy phases rise to phase-to-phase voltage (35kV) during the fault. 26/35kV cable has 10.5mm insulation versus 9.3mm for 21/35kV — a 13% thicker dielectric barrier. If your system uses resistance earthing, Petersen coil earthing, or operates unearthed, specify 26/35kV. For solidly-earthed 35kV utility networks, 21/35kV is sufficient.

Cable Construction

Three Core 26/35kV Cable Cross Section

1. Conductor — Stranded compacted circular copper or aluminium
2. Conductor Screen — Extruded semi-conductive compound
3. Insulation — XLPE, 10.5mm, 90°C rated
4. Insulation Screen — Extruded semi-conductive compound
5. Metallic Screen — Copper tape or concentric copper wires
6. Binder Tape — Non-hygroscopic
7. Filler — Non-hygroscopic
8. Outer Sheath — PVC Type ST2 (PE or LSZH)

Technical Characteristics

Rated Voltage U₀/U (Um)26/35kV (42kV maximum system voltage)
Governing StandardIEC 60840 (cables 30kV to 150kV)
Insulation Thickness10.5mm per core (all cross-sections)
Max. Conductor Temperature90°C (continuous), 250°C (short-circuit, max 5s)
Min. Bending Radius15 × overall diameter
Conductor TypesCopper or aluminium, compacted circular Class 2 per IEC 60228
Sheath OptionsPVC Type ST2, PE, or LSZH (BS 7835)
PD Test Voltage1.5U₀ (39kV) per IEC 60840 with extinction voltage measurement

Applicable Standards

StandardScope
IEC 60840Power cables with extruded insulation for rated voltages above 30kV up to 150kV. 26/35kV (Um=42kV) is governed by this standard.
GB/T 12706.2Chinese national standard for power cables 6kV to 35kV. 26/35kV is the highest voltage class in this standard.
BS 6622British standard for XLPE insulated cables. 26/35kV three-core covered under Part 1.
BS 7835LSZH sheathed MV/HV cables for fire-sensitive indoor installations.
IEC 60228Conductors — Class 2 stranded copper and aluminium, compacted circular.
26/35kV is specified where the system earthing arrangement demands higher U₀ rating. The key engineering question: is the 35kV system solidly earthed, or does it use a resistance/impedance earthing method? Solidly earthed → 21/35kV. Resistance earthed / unearthed / Petersen coil → 26/35kV. Incorrect U₀ selection in a resistance-earthed system leads to accelerated partial discharge activity during earth fault events, progressively degrading the XLPE insulation. For industrial and generator auxiliary systems where earth fault operation is a planned operating mode, 26/35kV is the mandatory specification.

Technical Specifications — Three Core 26/35kV

XLPE insulation: 10.5mm (all cross-sections). Ampacity values pre-calculated for three-core bundle. Air: 30°C. Soil: 20°C, 2.5 K·m/W, 0.7m depth. Conductor range starts at 50mm² for this voltage class.

Cross Section
(mm²)
Conductor
Dia. (mm)
Insulation
(mm)
Sheath
(mm)
Overall
Dia. (mm)
Weight Cu
(kg/km)
Weight Al
(kg/km)
Ampacity Air
Cu | Al (A)
Ampacity Soil
Cu | Al (A)
3 × 508.410.53.578.55,8424,909180 | 140190 | 145
3 × 7010.010.53.682.26,7245,418220 | 170230 | 180
3 × 9511.510.53.785.77,7545,982265 | 205275 | 215
3 × 12013.010.53.989.18,7866,547305 | 235315 | 245
3 × 15014.510.54.092.69,9577,159345 | 270355 | 275
3 × 18516.210.54.196.511,3047,853390 | 305400 | 310
3 × 24018.410.54.2101.513,3028,825455 | 355460 | 360
3 × 30020.510.54.4106.415,4219,824525 | 410520 | 410
3 × 40023.510.54.6113.318,81411,352600 | 470590 | 465
Source data note: Reference page lists standard IEC 60502 (not IEC 60840). Per IEC technical committee guidelines, 26/35kV (Um=42kV) falls under IEC 60840. Conductor range begins at 50mm² — cross-sections below 50mm² are available on request but are not commonly specified for 26/35kV due to the disproportionately large cable OD relative to the conductor cross-section.

Packaging & Delivery

🪵

Heavy-Duty Iron-Reinforced Drum

Reinforced wooden or steel drums. 3×400mm² Cu cable approaches 19 tonnes/km. Crane offloading mandatory at factory and site.

🛡️

Triple-Layer Moisture Protection

Per-core heat-shrink sealing + overall sheath end sealing + dual-layer caps with desiccant. UV-resistant drum wrap for outdoor storage up to 12 months.

📋

IEC 60840 Documentation

Per-core PD certificate (1.5U₀ = 39kV with extinction voltage), AC voltage test (2.5U₀ = 65kV/30min), DC resistance, full traceability.

Typical Applications — Three Core 26/35kV

🏭

Resistance-Earthed Industrial 35kV Systems

Primary application. Industrial MV networks with neutral earthing resistors (NER) where U₀=26kV is mandatory for earth fault operation.

Generator Auxiliary Systems

Power station auxiliary 35kV networks where generator ratings exceed 50MW and stability during earth faults requires 26/35kV rated cables.

🇨🇳

Chinese GB/T 12706.2 35kV Projects

Specified for 35kV infrastructure projects where system earthing analysis confirms resistance earthing or where project standards mandate the higher U₀ rating.

🌐

High-Reliability Substation Connections

132/35kV or 110/35kV substation interconnectors where continuous operation during a single earth fault is a contractual reliability requirement.

⛏️

Mining 35kV Distribution

Underground and open-pit mining 35kV networks with high earth fault risk due to cable damage likelihood. 26/35kV rating avoids cable replacement after fault-induced overvoltage.

🇷🇺

Russian & CIS Heavy Industry

Standard for Russian industrial 35kV networks where system earthing practices and cold climate operational requirements demand the highest U₀ rating available in three-core format.

Request a Quote

Ready to Work Together? Build a project with us!
This field is required.
This field is required.
Learn More From

Frequently Asked Questions

As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.

Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.

Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.

For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.

Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.

inquiry@qiangligroup.com +86 153 3220 6813