Factory-Direct Supply of Certified Wires and Conductors for Diverse Industrial Applications

Power Cable
E-YY power cable cross section structure, copper conductor with PVC insulation and outer sheath, industrial buried electrical wire

E-YY Cable

0,6/1kV Single or Multi Core PVC Insulated Heavy Current Cable

Conductor: Copper, solid (RE) or stranded (RM/SM) to EN 60228
Insulation: PVC
Sheath: PVC, black, UV-resistant, flame-retardant
Voltage: 600/1000V (0.6/1kV)
Number of cores: 1-5 cores per HD 308 S2
Package: Export wooden drum & iron wooden drum or as customer require
Standard: ÖVE-K 603, DIN EN 60228, HD 603 S1
Email: inquiry@qiangligroup.com

Product Overview

E-YY Cable is a 0.6/1kV PVC-insulated, PVC-sheathed unarmored power cable per the Austrian/German VDE designation system. The "E" prefix denotes a heavy-current power cable per VDE, and "YY" indicates PVC insulation + PVC sheath. It is widely used in Austria, Germany, and Central European markets for fixed indoor and outdoor power distribution where no mechanical protection is required. E-YY is functionally identical to NYY in Germany and CYKY in Poland — the designation differs only by national standard body, not by physical construction.

Regional Naming Equivalents

All of the following designations refer to the same cable construction (copper conductor, PVC insulation, PVC sheath, 0.6/1kV, unarmored):

RegionDesignationKey StandardNotes
Austria / VDE RegionE-YYÖVE-K 603, HD 603 S1E = heavy-current power cable, YY = PVC/PVC
Germany / DIN RegionNYYDIN VDE 0276-603Most common VDE designation for this construction
Poland / Central EuropeCYKYPNE 34 7659-3C = copper, Y = PVC insulation, K = cable
France / NFC RegionU-1000 R2VNF C 32-321PVC/PVC equivalent, often with numbered cores
ChinaVVGB/T 12706.1V = PVC insulation, V = PVC sheath
International / IECIEC 60502-1 PVC CableIEC 60502-1Generic international designation

Cable Construction

1

Copper Conductor

Bare copper, solid (RE, Class 1) for ≤10 mm² or stranded (RM/SM, Class 2) for ≥16 mm², per DIN EN 60228 / IEC 60228.

2

PVC Insulation

PVC compound per HD 603 S1. Continuous conductor temperature 70°C. Short-circuit temperature up to 160°C (max 5 seconds).

3

Core Filler / Bedding

PVC core covering or plastic binding tape applied over the laid-up cores for multi-core cables, ensuring roundness.

4

PVC Outer Sheath

PVC compound, black (standard), UV-resistant. Flame-retardant per EN 60332-1-2. Resistant to oils, acids, and moisture.

Technical Characteristics

Rated Voltage U₀/U600/1000V (0.6/1kV)
Test Voltage4 kV AC
Max. Conductor Temperature70°C (continuous), 160°C (short-circuit, max 5s)
Temperature Range (fixed)-20°C to +70°C
Temperature Range (installation)-5°C to +70°C (without pre-heating)
Min. Bending Radius15 × D (single-core), 12 × D (multi-core)
Flame RetardancyEN 60332-1-2 (single cable flame test)

Applicable Standards & Certifications

E-YY cables are manufactured to comply with the following standards. Qiangli can certify production to any combination of these based on project destination and local authority requirements.

StandardScope
ÖVE-K 603Austrian national standard for PVC-insulated heavy-current cables rated 0.6/1kV. The primary standard for E-YY designation.
HD 603 S1CENELEC Harmonization Document — base document for national standards across EU/EEA countries. All national variants (ÖVE, DIN VDE, PNE) are derived from HD 603.
DIN EN 60228 / IEC 60228Conductors of insulated cables — defines Class 1 (RE, solid) and Class 2 (RM/SM, stranded) conductor specifications.
HD 308 S2Core identification colors. Defines the color coding scheme used across CENELEC countries.
IEC 60502-1International standard for power cables with extruded insulation, 1kV to 30kV. Accepted in 90+ countries globally.
EN 60332-1-2Flame propagation test for single cable — E-YY meets this requirement for indoor fire safety.
DIN VDE 0276-603German equivalent standard (NYY cable). For projects in Germany, Austria, and Switzerland.
GB/T 12706.1Chinese national standard. VV (PVC/PVC) is the equivalent designation under this standard.
For project specification: E-YY is primarily specified in Austrian and German-speaking markets. For Polish projects, specify CYKY per PNE 34 7659-3. For broader EU projects, reference HD 603 S1. Test reports and Declaration of Performance (DoP) provided with every order.

Technical Specifications

RE = round solid conductor (Class 1). RM = round stranded (Class 2). SM = sector-shaped compacted stranded (Class 2). For cables marked "+" (e.g. 3×50/25), the second value is the reduced earth/neutral cross-section. Copper figure = copper weight per km of conductor only.

Single-Core E-YY Cable

Cross Section
× Cores
Conductor
Type
Copper Figure
(kg/km)
Outer Dia.
approx. (mm)
Weight
approx. (kg/km)
Current Rating
Ground (A)
Current Rating
Air (A)
1 × 16RE153.61125010784
1 × 25RM24012350138114
1 × 35RM33613460164139
1 × 50RM48015600195169
1 × 70RM67217820238213
1 × 95RM912191,080286264
1 × 120RM1,152211,310325307
1 × 150RM1,440231,600365352
1 × 185RM1,776252,000413406
1 × 240RM2,304282,500479483
1 × 300RM2,880303,180541557
1 × 400RM3,840323,670614646
1 × 500RM4,800344,380693747
1 × 630RM6,048425,620777858

2-Core E-YY Cable

Cross SectionTypeCopper (kg/km)Outer Dia. (mm)Weight (kg/km)Ground (A)Air (A)
2 × 1.5RE28.8112202720
2 × 2.5RE48.0122673625
2 × 4RE76.8143424734
2 × 6RE115.2154125943
2 × 10RE192165107959
2 × 16RM307.21867010279

3-Core E-YY Cable

Cross SectionTypeCopper (kg/km)Outer Dia. (mm)Weight (kg/km)Ground (A)Air (A)
3 × 1.5RE43.2112442720
3 × 2.5RE72.0122943625
3 × 4RE115.2143934734
3 × 6RE172.8154815943
3 × 10RE288166457959
3 × 16RE460.81887210279
3 × 16RM460.81987210279
3 × 25RM720211,350133106
3 × 35SM1,008221,460159129
3 × 50SM1,440261,750188157
3 × 70SM2,016292,400232199
3 × 95SM2,736333,560280246
3 × 120SM3,456374,310318285
3 × 150SM4,320415,310359326
3 × 185SM5,328476,630406374
3 × 240SM6,912528,480473445

3-Core + Reduced Earth/Neutral E-YY Cable

Cross SectionTypeCopper (kg/km)Outer Dia. (mm)Weight (kg/km)Ground (A)Air (A)
3 × 25 / 16RM / RE873.6221,513133106
3 × 35 / 16SM / RE1,161.6231,804159129
3 × 50 / 25SM / RM1,680282,349188157
3 × 70 / 35SM2,352323,117232199
3 × 95 / 50SM3,216364,167280246
3 × 120 / 70SM4,128395,190318285
3 × 150 / 70SM4,992436,161359326
3 × 185 / 95SM6,240507,673406374
3 × 240 / 120SM8,064569,850473445
3 × 300 / 150SM10,0806611,900535511

4-Core E-YY Cable

Cross SectionTypeCopper (kg/km)Outer Dia. (mm)Weight (kg/km)Ground (A)Air (A)
4 × 1.5RE57.6112782720
4 × 2.5RE96.0123403625
4 × 4RE153.6144604734
4 × 6RE230.4155705943
4 × 10RE384177757959
4 × 10RM384187757959
4 × 16RE614.4191,07210279
4 × 16RM614.4201,07210279
4 × 25RM960221,632133106
4 × 35SM1,344231,959159129
4 × 50SM1,920282,595188157
4 × 70SM2,688323,488232199
4 × 95SM3,648364,637280246
4 × 120SM4,608395,689318285
4 × 150SM5,760456,973359326
4 × 185SM7,104528,663406374
4 × 240SM9,2165811,140473445
Current rating notes: Ampacity values per HD 603 / IEC 60502-1 standard installation conditions (ground: 20°C soil, 2.5 K·m/W thermal resistivity, 0.7m depth; air: 30°C ambient). For installations with different conditions, apply derating factors per IEC 60364-5-52. Contact our engineering team for project-specific ampacity calculations.

Packaging & Delivery

🪵

Export Wooden Drum

Fumigated solid wood or plywood drums. Standard for all international shipments, suitable for container loading and sea freight.

🔩

Iron-Wooden Drum

Reinforced drums for heavy cable (120 mm² and above). Superior protection during transport and on-site handling.

📦

Custom Packaging

Plywood reels, coils (for small cross-sections), or customer-specified drum types on request. Custom marking included.

Customization Options

Full OEM/ODM service: custom core colors, sheath colors, cable marking/printing, private-label packaging, sequential meter marking. Minimum order quantities apply — contact our sales team for details.

Typical Applications

🏗️

Underground Distribution

Direct burial in soil, cable ducts, and underground conduits for residential and commercial power networks — where no mechanical stress is expected.

🏭

Industrial Plants

Fixed wiring in factories, processing plants, and switchgear rooms. Indoor cable trays, conduits, and surface-mounted installations.

🏢

Commercial Buildings

Main feeders and sub-distribution risers in office buildings, hospitals, schools, and shopping centers.

Power Stations

Auxiliary power cabling in generation plants and transformer substations. Indoor and outdoor protected cable routes.

🌊

Outdoor & Wet Locations

Suitable for outdoor installation in cable ducts, on walls, and in water — where permitted by local building codes.

🏠

Residential Supply

Building connection boxes to main distribution boards in apartment blocks and housing developments across Central Europe.

Request a Quote

Ready to Work Together? Build a project with us!
This field is required.
This field is required.
Learn More From

Frequently Asked Questions

As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.

Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.

Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.

For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.

Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.

inquiry@qiangligroup.com +86 153 3220 6813