E-YY Cable
Conductor: Copper, solid (RE) or stranded (RM/SM) to EN 60228
Insulation: PVC
Sheath: PVC, black, UV-resistant, flame-retardant
Voltage: 600/1000V (0.6/1kV)
Number of cores: 1-5 cores per HD 308 S2
Package: Export wooden drum & iron wooden drum or as customer require
Standard: ÖVE-K 603, DIN EN 60228, HD 603 S1
Email: inquiry@qiangligroup.com
Product Overview
E-YY Cable is a 0.6/1kV PVC-insulated, PVC-sheathed unarmored power cable per the Austrian/German VDE designation system. The "E" prefix denotes a heavy-current power cable per VDE, and "YY" indicates PVC insulation + PVC sheath. It is widely used in Austria, Germany, and Central European markets for fixed indoor and outdoor power distribution where no mechanical protection is required. E-YY is functionally identical to NYY in Germany and CYKY in Poland — the designation differs only by national standard body, not by physical construction.
Regional Naming Equivalents
All of the following designations refer to the same cable construction (copper conductor, PVC insulation, PVC sheath, 0.6/1kV, unarmored):
| Region | Designation | Key Standard | Notes |
|---|---|---|---|
| Austria / VDE Region | E-YY | ÖVE-K 603, HD 603 S1 | E = heavy-current power cable, YY = PVC/PVC |
| Germany / DIN Region | NYY | DIN VDE 0276-603 | Most common VDE designation for this construction |
| Poland / Central Europe | CYKY | PNE 34 7659-3 | C = copper, Y = PVC insulation, K = cable |
| France / NFC Region | U-1000 R2V | NF C 32-321 | PVC/PVC equivalent, often with numbered cores |
| China | VV | GB/T 12706.1 | V = PVC insulation, V = PVC sheath |
| International / IEC | IEC 60502-1 PVC Cable | IEC 60502-1 | Generic international designation |
Cable Construction
Copper Conductor
Bare copper, solid (RE, Class 1) for ≤10 mm² or stranded (RM/SM, Class 2) for ≥16 mm², per DIN EN 60228 / IEC 60228.
PVC Insulation
PVC compound per HD 603 S1. Continuous conductor temperature 70°C. Short-circuit temperature up to 160°C (max 5 seconds).
Core Filler / Bedding
PVC core covering or plastic binding tape applied over the laid-up cores for multi-core cables, ensuring roundness.
PVC Outer Sheath
PVC compound, black (standard), UV-resistant. Flame-retardant per EN 60332-1-2. Resistant to oils, acids, and moisture.
Technical Characteristics
| Rated Voltage U₀/U | 600/1000V (0.6/1kV) |
| Test Voltage | 4 kV AC |
| Max. Conductor Temperature | 70°C (continuous), 160°C (short-circuit, max 5s) |
| Temperature Range (fixed) | -20°C to +70°C |
| Temperature Range (installation) | -5°C to +70°C (without pre-heating) |
| Min. Bending Radius | 15 × D (single-core), 12 × D (multi-core) |
| Flame Retardancy | EN 60332-1-2 (single cable flame test) |
Applicable Standards & Certifications
E-YY cables are manufactured to comply with the following standards. Qiangli can certify production to any combination of these based on project destination and local authority requirements.
| Standard | Scope |
|---|---|
| ÖVE-K 603 | Austrian national standard for PVC-insulated heavy-current cables rated 0.6/1kV. The primary standard for E-YY designation. |
| HD 603 S1 | CENELEC Harmonization Document — base document for national standards across EU/EEA countries. All national variants (ÖVE, DIN VDE, PNE) are derived from HD 603. |
| DIN EN 60228 / IEC 60228 | Conductors of insulated cables — defines Class 1 (RE, solid) and Class 2 (RM/SM, stranded) conductor specifications. |
| HD 308 S2 | Core identification colors. Defines the color coding scheme used across CENELEC countries. |
| IEC 60502-1 | International standard for power cables with extruded insulation, 1kV to 30kV. Accepted in 90+ countries globally. |
| EN 60332-1-2 | Flame propagation test for single cable — E-YY meets this requirement for indoor fire safety. |
| DIN VDE 0276-603 | German equivalent standard (NYY cable). For projects in Germany, Austria, and Switzerland. |
| GB/T 12706.1 | Chinese national standard. VV (PVC/PVC) is the equivalent designation under this standard. |
Technical Specifications
RE = round solid conductor (Class 1). RM = round stranded (Class 2). SM = sector-shaped compacted stranded (Class 2). For cables marked "+" (e.g. 3×50/25), the second value is the reduced earth/neutral cross-section. Copper figure = copper weight per km of conductor only.
Single-Core E-YY Cable
| Cross Section × Cores |
Conductor Type |
Copper Figure (kg/km) |
Outer Dia. approx. (mm) |
Weight approx. (kg/km) |
Current Rating Ground (A) |
Current Rating Air (A) |
|---|---|---|---|---|---|---|
| 1 × 16 | RE | 153.6 | 11 | 250 | 107 | 84 |
| 1 × 25 | RM | 240 | 12 | 350 | 138 | 114 |
| 1 × 35 | RM | 336 | 13 | 460 | 164 | 139 |
| 1 × 50 | RM | 480 | 15 | 600 | 195 | 169 |
| 1 × 70 | RM | 672 | 17 | 820 | 238 | 213 |
| 1 × 95 | RM | 912 | 19 | 1,080 | 286 | 264 |
| 1 × 120 | RM | 1,152 | 21 | 1,310 | 325 | 307 |
| 1 × 150 | RM | 1,440 | 23 | 1,600 | 365 | 352 |
| 1 × 185 | RM | 1,776 | 25 | 2,000 | 413 | 406 |
| 1 × 240 | RM | 2,304 | 28 | 2,500 | 479 | 483 |
| 1 × 300 | RM | 2,880 | 30 | 3,180 | 541 | 557 |
| 1 × 400 | RM | 3,840 | 32 | 3,670 | 614 | 646 |
| 1 × 500 | RM | 4,800 | 34 | 4,380 | 693 | 747 |
| 1 × 630 | RM | 6,048 | 42 | 5,620 | 777 | 858 |
2-Core E-YY Cable
| Cross Section | Type | Copper (kg/km) | Outer Dia. (mm) | Weight (kg/km) | Ground (A) | Air (A) |
|---|---|---|---|---|---|---|
| 2 × 1.5 | RE | 28.8 | 11 | 220 | 27 | 20 |
| 2 × 2.5 | RE | 48.0 | 12 | 267 | 36 | 25 |
| 2 × 4 | RE | 76.8 | 14 | 342 | 47 | 34 |
| 2 × 6 | RE | 115.2 | 15 | 412 | 59 | 43 |
| 2 × 10 | RE | 192 | 16 | 510 | 79 | 59 |
| 2 × 16 | RM | 307.2 | 18 | 670 | 102 | 79 |
3-Core E-YY Cable
| Cross Section | Type | Copper (kg/km) | Outer Dia. (mm) | Weight (kg/km) | Ground (A) | Air (A) |
|---|---|---|---|---|---|---|
| 3 × 1.5 | RE | 43.2 | 11 | 244 | 27 | 20 |
| 3 × 2.5 | RE | 72.0 | 12 | 294 | 36 | 25 |
| 3 × 4 | RE | 115.2 | 14 | 393 | 47 | 34 |
| 3 × 6 | RE | 172.8 | 15 | 481 | 59 | 43 |
| 3 × 10 | RE | 288 | 16 | 645 | 79 | 59 |
| 3 × 16 | RE | 460.8 | 18 | 872 | 102 | 79 |
| 3 × 16 | RM | 460.8 | 19 | 872 | 102 | 79 |
| 3 × 25 | RM | 720 | 21 | 1,350 | 133 | 106 |
| 3 × 35 | SM | 1,008 | 22 | 1,460 | 159 | 129 |
| 3 × 50 | SM | 1,440 | 26 | 1,750 | 188 | 157 |
| 3 × 70 | SM | 2,016 | 29 | 2,400 | 232 | 199 |
| 3 × 95 | SM | 2,736 | 33 | 3,560 | 280 | 246 |
| 3 × 120 | SM | 3,456 | 37 | 4,310 | 318 | 285 |
| 3 × 150 | SM | 4,320 | 41 | 5,310 | 359 | 326 |
| 3 × 185 | SM | 5,328 | 47 | 6,630 | 406 | 374 |
| 3 × 240 | SM | 6,912 | 52 | 8,480 | 473 | 445 |
3-Core + Reduced Earth/Neutral E-YY Cable
| Cross Section | Type | Copper (kg/km) | Outer Dia. (mm) | Weight (kg/km) | Ground (A) | Air (A) |
|---|---|---|---|---|---|---|
| 3 × 25 / 16 | RM / RE | 873.6 | 22 | 1,513 | 133 | 106 |
| 3 × 35 / 16 | SM / RE | 1,161.6 | 23 | 1,804 | 159 | 129 |
| 3 × 50 / 25 | SM / RM | 1,680 | 28 | 2,349 | 188 | 157 |
| 3 × 70 / 35 | SM | 2,352 | 32 | 3,117 | 232 | 199 |
| 3 × 95 / 50 | SM | 3,216 | 36 | 4,167 | 280 | 246 |
| 3 × 120 / 70 | SM | 4,128 | 39 | 5,190 | 318 | 285 |
| 3 × 150 / 70 | SM | 4,992 | 43 | 6,161 | 359 | 326 |
| 3 × 185 / 95 | SM | 6,240 | 50 | 7,673 | 406 | 374 |
| 3 × 240 / 120 | SM | 8,064 | 56 | 9,850 | 473 | 445 |
| 3 × 300 / 150 | SM | 10,080 | 66 | 11,900 | 535 | 511 |
4-Core E-YY Cable
| Cross Section | Type | Copper (kg/km) | Outer Dia. (mm) | Weight (kg/km) | Ground (A) | Air (A) |
|---|---|---|---|---|---|---|
| 4 × 1.5 | RE | 57.6 | 11 | 278 | 27 | 20 |
| 4 × 2.5 | RE | 96.0 | 12 | 340 | 36 | 25 |
| 4 × 4 | RE | 153.6 | 14 | 460 | 47 | 34 |
| 4 × 6 | RE | 230.4 | 15 | 570 | 59 | 43 |
| 4 × 10 | RE | 384 | 17 | 775 | 79 | 59 |
| 4 × 10 | RM | 384 | 18 | 775 | 79 | 59 |
| 4 × 16 | RE | 614.4 | 19 | 1,072 | 102 | 79 |
| 4 × 16 | RM | 614.4 | 20 | 1,072 | 102 | 79 |
| 4 × 25 | RM | 960 | 22 | 1,632 | 133 | 106 |
| 4 × 35 | SM | 1,344 | 23 | 1,959 | 159 | 129 |
| 4 × 50 | SM | 1,920 | 28 | 2,595 | 188 | 157 |
| 4 × 70 | SM | 2,688 | 32 | 3,488 | 232 | 199 |
| 4 × 95 | SM | 3,648 | 36 | 4,637 | 280 | 246 |
| 4 × 120 | SM | 4,608 | 39 | 5,689 | 318 | 285 |
| 4 × 150 | SM | 5,760 | 45 | 6,973 | 359 | 326 |
| 4 × 185 | SM | 7,104 | 52 | 8,663 | 406 | 374 |
| 4 × 240 | SM | 9,216 | 58 | 11,140 | 473 | 445 |
Packaging & Delivery
Export Wooden Drum
Fumigated solid wood or plywood drums. Standard for all international shipments, suitable for container loading and sea freight.
Iron-Wooden Drum
Reinforced drums for heavy cable (120 mm² and above). Superior protection during transport and on-site handling.
Custom Packaging
Plywood reels, coils (for small cross-sections), or customer-specified drum types on request. Custom marking included.
Customization Options
Full OEM/ODM service: custom core colors, sheath colors, cable marking/printing, private-label packaging, sequential meter marking. Minimum order quantities apply — contact our sales team for details.
Typical Applications
Underground Distribution
Direct burial in soil, cable ducts, and underground conduits for residential and commercial power networks — where no mechanical stress is expected.
Industrial Plants
Fixed wiring in factories, processing plants, and switchgear rooms. Indoor cable trays, conduits, and surface-mounted installations.
Commercial Buildings
Main feeders and sub-distribution risers in office buildings, hospitals, schools, and shopping centers.
Power Stations
Auxiliary power cabling in generation plants and transformer substations. Indoor and outdoor protected cable routes.
Outdoor & Wet Locations
Suitable for outdoor installation in cable ducts, on walls, and in water — where permitted by local building codes.
Residential Supply
Building connection boxes to main distribution boards in apartment blocks and housing developments across Central Europe.
Request a Quote
Frequently Asked Questions
As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.
Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.
Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.
For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.
Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.