Factory-Direct Supply of Certified Wires and Conductors for Diverse Industrial Applications
ZR-YJV Cable
Conductor: Annealed copper or aluminum, Class 1/2 to GB/T 3956
Insulation: XLPE (YJ), rated 90°C, flame-retardant per GB/T 18380
Sheath: PVC compound (V), black, flame-retardant
Voltage: 0.6/1kV
Number of cores: 2-4 cores per GB/T 12706.1
Package: Export wooden drum & iron wooden drum or as customer require
Standard: GB/T 12706.1, IEC 60502-1
Product Overview
ZR-YJV Cable is a flame-retardant 0.6/1kV power cable with XLPE insulation and PVC sheath, manufactured per China's national standard GB/T 12706.1. The designation follows Chinese cable naming convention: ZR = flame retardant, YJ = XLPE insulation, V = PVC sheath. It is available in both copper (Cu) and aluminum (Al) conductor variants, making it the dominant power cable type in China's domestic construction and industrial markets as well as Belt & Road export projects.
Flame Retardant Classification
ZR-YJV is tested per GB/T 18380 (equivalent to IEC 60332) for flame propagation. The ZR designation can be further specified to tighter sub-classes:
| Designation | Flame Retardant Class | Test Standard | Typical Application |
|---|---|---|---|
| ZR-YJV (ZR) | General flame retardant — Grade C | GB/T 18380.33 / IEC 60332-3-23 | Standard commercial buildings, indoor cable trays |
| ZB-YJV (ZB) | Enhanced flame retardant — Grade B | GB/T 18380.34 / IEC 60332-3-22 | High-occupancy buildings, hospitals, data centers |
| ZA-YJV (ZA) | Highest flame retardant — Grade A | GB/T 18380.35 / IEC 60332-3-21 | Critical infrastructure, subways, tunnels, nuclear plants |
Copper vs Aluminum Conductor
ZR-YJV is widely available in both conductor materials. The choice depends on project budget, weight constraints, and termination requirements:
| Property | Copper (Cu) | Aluminum (Al) |
|---|---|---|
| Conductivity (IACS) | 100% | ~61% |
| Weight (same ampacity) | Reference | ~50% lighter |
| Cost (same ampacity) | Higher | ~40-60% lower |
| Corrosion Resistance | Excellent — self-passivating | Good — requires proper termination with anti-oxidation compound |
| Termination | Standard copper lugs | Requires bi-metallic Cu/Al lugs |
| Typical Market | Critical circuits, short runs, marine | Bulk distribution, long runs, cost-driven projects |
Regional Naming Equivalents
ZR-YJV is the Chinese GB/T designation. The same physical construction is known by different names globally. All have XLPE insulation + PVC sheath, flame-retardant:
| Region | Designation | Key Standard |
|---|---|---|
| China | ZR-YJV / ZB-YJV / ZA-YJV | GB/T 12706.1 |
| Germany / DIN-VDE | N2XY | DIN VDE 0276-603 |
| France / NFC | CV TFR-CV | NF C 32-321 |
| International / IEC | IEC 60502-1 FR-XLPE/PVC | IEC 60502-1 + IEC 60332-3 |
| UK | BS 5467 FR XLPE/PVC | BS 5467 + BS EN 60332-3 |
Cable Construction
Conductor (Cu or Al)
Annealed copper or aluminum, Class 1 (solid) or Class 2 (stranded) per GB/T 3956. Aluminum with anti-oxidation treatment.
XLPE Insulation (YJ)
Cross-linked polyethylene, 90°C continuous, 250°C short-circuit. Flame-retardant grade per GB/T 18380.
Core Assembly
Laid-up cores with non-hygroscopic PP filler. PVC inner covering or binding tape for circular cross-section.
PVC Sheath (V)
PVC compound, black (standard). Flame-retardant, oil-resistant. Other colors available: red, yellow, blue, green per GB/T 6995.
Technical Characteristics
| Rated Voltage | 0.6/1kV (U₀/U) |
| Max. Conductor Temperature | 90°C (continuous), 250°C (short-circuit, max 5s) |
| Min. Installation Temperature | 0°C (without pre-heating) |
| Min. Bending Radius | 20 × D (single-core), 15 × D (multi-core) |
| Flame Retardant Class | ZR (Grade C), ZB (Grade B), ZA (Grade A) per GB/T 18380 |
| Conductor Standard | GB/T 3956 (equivalent to IEC 60228) |
| Sheath Color | Black (standard); red, yellow, blue, green per GB/T 6995 |
Applicable Standards & Certifications
ZR-YJV cables are manufactured to GB/T 12706.1 and can also be certified to international equivalents for export projects.
| Standard | Scope |
|---|---|
| GB/T 12706.1 | Chinese national standard — power cables with extruded insulation for rated voltages 1kV to 35kV. The primary standard governing ZR-YJV. |
| GB/T 18380 / IEC 60332-3 | Flame retardant classification — defines Grades A, B, C for bundled cable flame tests. |
| GB/T 3956 / IEC 60228 | Conductor specification — copper and aluminum, Class 1 (solid) and Class 2 (stranded). |
| IEC 60502-1 | International standard for power cables 1kV-30kV. ZR-YJV meets IEC 60502-1 with additional flame retardant requirements. |
| DIN VDE 0276-603 | German equivalent standard (N2XY). For projects in Germany and Central Europe. |
| BS 5467 | British standard for XLPE insulated unarmored cables. For projects in UK and Commonwealth markets. |
| AS/NZS 5000.1 | Australia/New Zealand standard. Qiangli can manufacture to this standard on request. |
| GB/T 6995 | Sheath and core identification color marking for Chinese-standard cables. |
Core Identification (per GB/T 6995)
| Number of Cores | Standard Core Colors (GB/T 6995) | Alternative Scheme |
|---|---|---|
| 1-core | Black or Brown | — |
| 2-core | Red, Blue | Blue, Brown |
| 3-core | Red, Yellow, Blue | Brown, Black, Grey |
| 4-core | Red, Yellow, Blue, Green | Blue, Brown, Black, Grey |
| 5-core | Red, Yellow, Blue, Green + Yellow/Green | Blue, Brown, Black, Grey + Yellow/Green |
Technical Specifications
All values per GB/T 12706.1. Cu = copper conductor; Al = aluminum conductor. Sections marked "*" use solid (Class 1) conductor per GB/T 3956. For aluminum conductor cables, add "YJLV" to the order designation. Flame retardant class defaults to ZR (Grade C) unless ZB or ZA is specified.
2-Core ZR-YJV Cable
| Cross Section (mm²) | Conductor Dia. (mm) | Insulation (mm) | Sheath (mm) | Overall Dia. (mm) | Weight Cu (kg/km) | Weight Al (kg/km) |
|---|---|---|---|---|---|---|
| 2 × 1.5 | 1.38 | 0.7 | 1.8 | 9.8 | 111 | — |
| 2 × 2.5 | 1.78 | 0.7 | 1.8 | 10.6 | 136 | 106 |
| 2 × 4 | 2.25 | 0.7 | 1.8 | 11.5 | 182 | 134 |
| 2 × 6 | 2.76 | 0.7 | 1.8 | 12.5 | 227 | — |
| *2 × 6 | 2.83 | 0.7 | 1.8 | 12.7 | — | 159 |
| 2 × 10 | 4.05 | 0.7 | 1.8 | 15.1 | 338 | 216 |
| 2 × 16 | 5.10 | 0.7 | 1.8 | 17.2 | 480 | 285 |
| 2 × 25 | 5.90 | 0.9 | 1.8 | 19.6 | 664 | 360 |
| 2 × 35 | 6.90 | 0.9 | 1.8 | 21.6 | 869 | 445 |
| 2 × 50 | 9.37 | 1.0 | 1.8 | 19.4 | 1,037 | 464 |
| 2 × 70 | 11.20 | 1.1 | 1.8 | 22.1 | 1,456 | 621 |
| 2 × 95 | 13.23 | 1.1 | 1.9 | 24.8 | 1,959 | 806 |
| 2 × 120 | 14.92 | 1.2 | 2.0 | 27.2 | 2,451 | 994 |
| 2 × 150 | 16.44 | 1.4 | 2.2 | 30.7 | 3,047 | 1,259 |
| 2 × 185 | 18.49 | 1.6 | 2.3 | 33.7 | 3,789 | 1,549 |
| 2 × 240 | 21.40 | 1.7 | 2.5 | 38.9 | 4,941 | 1,974 |
| 2 × 300 | 24.10 | 1.8 | 2.6 | 42.7 | 6,125 | 2,417 |
| 2 × 400 | 27.20 | 2.0 | 2.9 | 48.1 | 7,837 | 3,071 |
| 2 × 500 | 31.00 | 2.2 | 3.1 | 53.6 | 10,010 | 3,882 |
3-Core ZR-YJV Cable
| Cross Section (mm²) | Conductor Dia. (mm) | Insulation (mm) | Sheath (mm) | Overall Dia. (mm) | Weight Cu (kg/km) | Weight Al (kg/km) |
|---|---|---|---|---|---|---|
| 3 × 1.5 | 1.38 | 0.7 | 1.8 | 10.2 | 130 | — |
| 3 × 2.5 | 1.78 | 0.7 | 1.8 | 11.1 | 168 | 124 |
| 3 × 4 | 2.25 | 0.7 | 1.8 | 12.1 | 224 | 151 |
| 3 × 6 | 2.76 | 0.7 | 1.8 | 13.2 | 290 | — |
| *3 × 6 | 2.83 | 0.7 | 1.8 | 13.3 | — | 189 |
| 3 × 10 | 4.05 | 0.7 | 1.8 | 16.0 | 440 | 257 |
| 3 × 16 | 5.10 | 0.7 | 1.8 | 18.2 | 633 | 341 |
| 3 × 25 | 5.90 | 0.9 | 1.8 | 20.8 | 912 | 456 |
| 3 × 35 | 6.90 | 0.9 | 1.8 | 23.0 | 1,207 | 571 |
| 3 × 50 | 9.34 | 1.0 | 1.8 | 25.4 | 1,532 | 672 |
| 3 × 70 | 11.22 | 1.1 | 1.9 | 28.8 | 2,166 | 913 |
| 3 × 95 | 13.16 | 1.1 | 2.0 | 32.4 | 2,917 | 1,188 |
| 3 × 120 | 14.76 | 1.2 | 2.1 | 35.3 | 3,648 | 1,462 |
| 3 × 150 | 16.34 | 1.4 | 2.3 | 38.7 | 4,505 | 1,823 |
| 3 × 185 | 18.30 | 1.6 | 2.4 | 42.4 | 5,606 | 2,245 |
| 3 × 240 | 20.92 | 1.7 | 2.6 | 47.2 | 7,237 | 2,826 |
| 3 × 300 | 23.38 | 1.8 | 2.7 | 51.5 | 8,986 | 3,472 |
| 3 × 400 | 26.46 | 2.0 | 3.0 | 57.5 | 11,594 | 4,444 |
| 3 × 500 | 30.00 | 2.2 | 3.2 | 64.3 | 14,809 | 5,617 |
3+1 Core ZR-YJV Cable
Three phase conductors + one reduced neutral. Phase and earth columns list conductor diameters and insulation thicknesses respectively. Weight is total cable weight.
| Cross Section (mm²) | Conductor Dia. Phase/Earth (mm) | Insulation Phase/Earth (mm) | Sheath (mm) | Overall Dia. (mm) | Weight Cu (kg/km) | Weight Al (kg/km) |
|---|---|---|---|---|---|---|
| 3 × 2.5 + 1 × 1.5 | 1.78/1.38 | 0.7/0.7 | 1.8 | 11.7 | 190 | — |
| 3 × 4 + 1 × 2.5 | 2.25/1.78 | 0.7/0.7 | 1.8 | 12.7 | 257 | 169 |
| 3 × 6 + 1 × 4 | 2.76/2.25 | 0.7/0.7 | 1.8 | 14.0 | 339 | — |
| *3 × 6 + *1 × 4 | 2.83/2.25 | 0.7/0.7 | 1.8 | 14.1 | — | 213 |
| 3 × 10 + 1 × 6 | 4.05/2.76 | 0.7/0.7 | 1.8 | 16.6 | 506 | — |
| *3 × 10 + *1 × 6 | 4.05/2.83 | 0.7/0.7 | 1.8 | 16.7 | — | 289 |
| 3 × 16 + 1 × 10 | 5.10/4.05 | 0.7/0.7 | 1.8 | 19.3 | 743 | 390 |
| 3 × 25 + 1 × 16 | 5.90/5.10 | 0.9/0.7 | 1.8 | 22.1 | 1,085 | 532 |
| 3 × 35 + *1 × 16 | 6.90/5.10 | 0.9/0.7 | 1.8 | 23.9 | 1,374 | 641 |
| 3 × 50 + 1 × 25 | 9.10/5.90 | 1.0/0.9 | 1.8 | 25.4 | 1,787 | 775 |
| 3 × 70 + 1 × 35 | 10.94/6.90 | 1.1/0.9 | 1.8 | 29.4 | 2,506 | 1,042 |
| 3 × 95 + 1 × 50 | 12.91/9.00 | 1.1/1.0 | 1.8 | 32.8 | 3,360 | 1,345 |
| 3 × 120 + 1 × 70 | 14.51/10.83 | 1.2/1.1 | 1.9 | 36.0 | 4,293 | 1,688 |
| 3 × 150 + *1 × 70 | 16.11/10.83 | 1.4/1.1 | 2.1 | 39.4 | 5,122 | 2,023 |
| 3 × 185 + 1 × 95 | 18.04/12.17 | 1.6/1.1 | 2.2 | 43.3 | 6,453 | 2,516 |
| 3 × 240 + 1 × 120 | 20.65/14.39 | 1.7/1.2 | 2.3 | 48.4 | 8,332 | 3,192 |
| 3 × 300 + 1 × 150 | 23.08/15.93 | 1.8/1.4 | 2.5 | 53.3 | 10,335 | 3,927 |
| 3 × 400 + 1 × 185 | 25.49/17.77 | 2.0/1.6 | 2.7 | 59.4 | 13,251 | 4,982 |
4-Core ZR-YJV Cable
| Cross Section (mm²) | Conductor Dia. (mm) | Insulation (mm) | Sheath (mm) | Overall Dia. (mm) | Weight Cu (kg/km) | Weight Al (kg/km) |
|---|---|---|---|---|---|---|
| 4 × 1.5 | 1.40 | 0.7 | 1.8 | 10.9 | 157 | — |
| 4 × 2.5 | 1.80 | 0.7 | 1.8 | 11.9 | 202 | 143 |
| 4 × 4 | 2.30 | 0.7 | 1.8 | 13.0 | 270 | 173 |
| 4 × 6 | 2.80 | 0.7 | 1.8 | 14.3 | 361 | — |
| *4 × 6 | 2.80 | 0.7 | 1.8 | 14.4 | — | 225 |
| 4 × 10 | 4.10 | 0.7 | 1.8 | 17.4 | 552 | 308 |
| 4 × 16 | 5.10 | 0.7 | 1.8 | 19.9 | 802 | 414 |
| 4 × 25 | 5.90 | 0.9 | 1.8 | 22.8 | 1,157 | 549 |
| 4 × 35 | 6.90 | 0.9 | 1.8 | 25.3 | 1,541 | 693 |
| 4 × 50 | 9.10 | 1.0 | 1.8 | 25.5 | 1,973 | 827 |
| 4 × 70 | 11.00 | 1.1 | 2.0 | 29.6 | 2,823 | 1,153 |
| 4 × 95 | 12.90 | 1.1 | 2.1 | 33.4 | 3,812 | 1,507 |
| 4 × 120 | 14.50 | 1.2 | 2.3 | 37.0 | 4,797 | 1,881 |
| 4 × 150 | 16.10 | 1.4 | 2.4 | 41.1 | 5,920 | 2,344 |
| 4 × 185 | 18.00 | 1.6 | 2.6 | 45.5 | 7,400 | 2,920 |
| 4 × 240 | 20.60 | 1.7 | 2.8 | 51.3 | 9,611 | 3,730 |
| 4 × 300 | 23.00 | 1.8 | 3.0 | 56.4 | 11,927 | 4,575 |
| 4 × 400 | 26.10 | 2.0 | 3.3 | 63.2 | 15,377 | 5,845 |
| 4 × 500 | 29.50 | 2.2 | 3.5 | 73.8 | 19,711 | 7,455 |
Packaging & Delivery
Export Wooden Drum
Fumigated solid wood or plywood drums. Standard for international sea freight and container loading.
Iron-Wooden Drum
Reinforced composite drums for heavy cables (120 mm²+). Superior protection during transport.
Custom Packaging
Plywood reels, customer-specified drum types, custom marking, and private-label packaging on request.
Customization Options
Full OEM/ODM: copper or aluminum conductor, custom core colors (GB/T 6995 or HD 308), custom sheath colors, sequential meter marking, private-label packaging. Contact sales for MOQ.
Typical Applications
ZR-YJV is the workhorse XLPE power cable in China and is widely exported to Belt & Road and developing markets:
Construction & Infrastructure
Main electrical distribution in residential towers, commercial complexes, metro stations, and airport terminals.
Industrial Parks
Factory power supply and inter-building distribution in manufacturing zones. Aluminum variant popular for cost-sensitive long runs.
Utility Distribution
Secondary distribution networks. Copper for critical feeders, aluminum for bulk distribution lines.
Government & Public Buildings
Schools, hospitals, and government facilities. ZB-YJV (Grade B) specified where enhanced fire safety is required.
Transportation Infrastructure
Railway stations, subway systems, and tunnels where ZA-YJV (Grade A) flame retardant cables are mandated.
Belt & Road Export Projects
Infrastructure projects in Africa, Southeast Asia, and South America accepting GB/T 12706.1 with IEC 60502-1 equivalency.
Request a Quote
Frequently Asked Questions
As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.
Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.
Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.
For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.
Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.