Factory-Direct Supply of Certified Wires and Conductors for Diverse Industrial Applications

Power Cable

N2XBY Cable

Power cable 0,6/1 kV with Cu conductors, XLPE insulated and PVC sheathed

Conductor: Copper, Class 1 or 2 to EN 60228
Insulation: XLPE (2X), rated 90°C
Armour: Non-magnetic steel tape (0.2 or 0.5mm)
Sheath: PVC compound 5V-90, black
Voltage: 0.6/1kV
Number of cores: 1-5 cores, 3+1, 4+1, 3+2
Package: Export wooden drum & iron wooden drum

Product Overview

N2XBY Cable is a 0.6/1kV XLPE-insulated power cable with non-magnetic steel tape armor and PVC sheath. VDE naming: N = standard, 2X = XLPE, B = steel tape armor, Y = PVC sheath. It is the cost-optimized armored cable in the VDE family — delivering the mechanical protection of double steel tape with the proven reliability of PVC compound 5V-90 as the outer sheath. N2XBY is the most widely specified armored cable for general industrial, commercial, and utility applications across Central Europe and export markets.

Cable Construction

N2XBY Cable Cross Section

1. Conductor — Copper, Class 1 or 2
2. XLPE Insulation — 90°C rated
3. Filler — Non-hygroscopic PP
4. Binder Tape — Core assembly
5. Inner Sheath — PVC bedding
6. Armor — Non-magnetic steel tape
7. Outer Sheath — PVC 5V-90

Technical Characteristics

Rated Voltage0.6/1kV
Max. Conductor Temperature90°C (continuous), 250°C (short-circuit)
Min. Installation Temperature-5°C
Min. Bending Radius15 × D (single), 12 × D (multi)
Armor TypeNon-magnetic steel tape (0.2mm or 0.5mm)
SheathPVC 5V-90, black

Armored Cable Comparison

Three steel-tape armored cables in the VDE family — same XLPE insulation + steel tape armor, different sheath materials for different environments:

PropertyN2XBY (PVC)N2XB2Y (HDPE)N2XBH (HFFR/LSZH)
SheathPVC 5V-90HDPE (2Y)HFFR / LSZH (H)
Moisture ResistanceGoodExcellentGood
Fire SafetyStandardStandardLow smoke, no halogen
CostLowestMediumHighest
Primary MarketGeneral industrial, commercialDirect burial, wet soilHospitals, schools, tunnels
Selection rule: N2XBY (PVC) for standard above-ground and duct installations. N2XB2Y (HDPE) for direct burial and permanent moisture. N2XBH (LSZH) where building fire codes require halogen-free cables. All three share identical conductor, insulation, and armor construction.

Applicable Standards

StandardScope
DIN VDE 0276-603German national standard for XLPE/PVC armored power cables.
IEC 60502-1International standard — 90+ countries accept this certification.
HD 603 S1CENELEC base document for all national cable standards in EU/EEA.
EN 60228 / IEC 60228Conductor specification — Class 1 and Class 2.
BS 5467British standard for XLPE insulated armored cables.
GB/T 12706.1Chinese standard — YJV22 (STA/PVC) is the closest equivalent.

Technical Specifications

Armor thickness: 0.2mm for cross-sections ≤70mm²; 0.5mm for ≥95mm². Current ratings: air 30°C, ground 20°C, 2.5 K·m/W, 0.7m depth. "-" = not specified.

1-Core N2XBY Cable

Cross Section
(mm²)
Insulation
(mm)
Armor
(mm)
Sheath
(mm)
Outer Dia.
(mm)
Weight
(kg/km)
DC Resistance
at 20°C (Ω/km)
Current
Air (A)
Current
Ground (A)
1 × 100.70.21.811.82441.837547
1 × 160.70.21.812.93181.159762
1 × 250.90.21.814.64300.72712578
1 × 350.90.21.815.25330.52415594
1 × 501.00.21.816.76680.387190110
1 × 701.10.21.818.58930.268245135
1 × 951.10.21.820.11,1570.193300160
1 × 1201.20.21.821.71,4100.153350185
1 × 1501.40.21.823.71,7050.124400205
1 × 1851.60.21.825.72,0820.0991460235
1 × 2401.70.21.828.02,6520.0754
1 × 3001.80.21.931.03,2590.0601
1 × 4002.00.22.035.04,1350.047

2-Core N2XBY Cable

Cross Section
(mm²)
Insul.
(mm)
Armor
(mm)
Sheath
(mm)
O.D.
(mm)
Weight
(kg/km)
20°C Res.
(Ω/km)
Air
(A)
Ground
(A)
2 × 2.50.70.21.813.42307.4145
2 × 40.70.21.814.32774.6159
2 × 60.70.21.815.33363.0874
2 × 100.70.21.817.84521.8364100
2 × 160.70.21.820.06091.1583135
2 × 250.90.21.823.38450.727110165
2 × 350.90.21.824.61,0650.524135200
2 × 501.00.21.827.21,2970.387165240
2 × 701.10.21.931.41,7750.268210295
2 × 951.10.22.035.52,3400.193260355
2 × 1201.20.52.240.23,2380.153305405
2 × 1501.40.52.344.23,9710.124345455
2 × 1851.60.52.548.94,8450.0991396515

3-Core N2XBY Cable

Cross Section
(mm²)
Insul.
(mm)
Armor
(mm)
Sheath
(mm)
O.D.
(mm)
Weight
(kg/km)
20°C Res.
(Ω/km)
Air
(A)
Ground
(A)
3 × 2.50.70.21.813.92657.4135
3 × 40.70.21.814.83284.6150
3 × 60.70.21.816.04103.0860
3 × 100.70.21.818.65601.836485
3 × 160.90.21.821.07751.1583110
3 × 250.90.21.824.61,0980.727110140
3 × 350.90.21.826.01,4100.524135170
3 × 501.00.21.928.91,7800.387165200
3 × 701.10.22.033.92,4750.268210245
3 × 951.10.52.239.03,2600.193260300
3 × 1201.20.52.342.74,4770.153305335
3 × 1501.40.52.447.55,4400.124345380
3 × 1851.60.52.652.16,7070.0991395430
3 × 2401.70.52.858.38,5330.0754465500
3 × 3001.80.52.963.610,4550.0601535565

4-Core N2XBY Cable

Cross Section
(mm²)
Insul.
(mm)
Armor
(mm)
Sheath
(mm)
O.D.
(mm)
Weight
(kg/km)
20°C Res.
(Ω/km)
Air
(A)
Ground
(A)
4 × 2.50.70.21.814.73087.4135
4 × 40.70.21.815.83884.6150
4 × 60.70.21.817.04883.0860
4 × 100.70.21.820.06811.836485
4 × 160.90.21.822.79601.1583110
4 × 250.90.21.826.71,3750.727110140
4 × 350.90.21.828.31,7790.524135170
4 × 501.00.22.132.02,2960.387165200
4 × 701.10.52.138.53,1750.268210245
4 × 951.10.52.342.94,6650.193260300
4 × 1201.20.52.447.45,7280.153305335
4 × 1501.40.52.652.36,9990.124345380
4 × 1851.60.52.757.58,6570.0991395430
4 × 2401.70.53.064.311,0000.0754465500
4 × 3001.80.53.170.313,5870.0601535565

5-Core, 3+1, 4+1, 3+2 Core

The following configurations are available. Specifications cover reduced neutral/earth configurations for balanced and unbalanced 3-phase systems:

Cross Section
(mm²)
Insul.
(mm)
Armor
(mm)
Sheath
(mm)
O.D.
(mm)
Weight
(kg/km)
20°C Res.
(Ω/km)
Air
(A)
Ground
(A)
5-Core
5 × 2.50.70.21.815.63507.4135
5 × 40.70.21.816.84474.6150
5 × 60.70.21.818.25693.0860
5 × 100.70.21.821.68051.836485
5 × 160.70.21.824.61,1501.1583110
5 × 250.90.21.829.01,6550.727110140
5 × 350.90.21.931.02,1660.524135170
5 × 501.00.22.135.72,9450.387165200
5 × 701.10.52.342.44,4530.268210245
5 × 951.10.52.447.25,8620.193260300
5 × 1201.20.52.651.87,1760.153305335
5 × 1501.40.52.757.68,7700.124345380
5 × 1851.60.52.963.810,8270.0991395430
5 × 2401.70.53.270.713,7700.0754465500
5 × 3001.80.53.478.016,9600.0601535565
3+1 Core
3 × 4 + 1 × 2.50.7/0.70.21.815.53684.61/7.4150
3 × 6 + 1 × 40.7/0.70.21.816.84653.08/4.6160
3 × 10 + 1 × 60.7/0.70.21.819.36331.83/3.086485
3 × 16 + 1 × 100.7/0.70.21.822.18901.15/1.8383110
3 × 25 + 1 × 160.9/0.70.21.825.11,2720.727/1.15110140
3 × 35 + 1 × 160.9/0.70.21.826.81,5830.524/1.15135170
3 × 50 + 1 × 251/0.90.21.930.22,0300.387/0.727165200
3 × 70 + 1 × 351.1/0.90.22.035.12,8100.268/0.524210245
3 × 95 + 1 × 501.1/1.00.52.240.44,1350.193/0.387260300
3 × 120 + 1 × 701.2/1.10.52.345.05,1350.153/0.268305335
3 × 150 + 1 × 701.4/1.10.52.549.16,1200.124/0.268345380
3 × 185 + 1 × 951.6/1.10.52.854.37,6160.0991/0.193395430
3 × 240 + 1 × 1201.7/1.20.52.859.19,6790.0754/0.153465500
3 × 300 + 1 × 1501.8/1.40.53.066.011,8890.0601/0.124535565
4+1 Core
4 × 4 + 1 × 2.50.7/0.70.21.816.34344.61/7.4150
4 × 6 + 1 × 40.7/0.70.21.817.75493.08/4.6160
4 × 10 + 1 × 60.7/0.70.21.820.37591.83/3.086485
4 × 16 + 1 × 100.7/0.70.21.824.01,0791.15/1.8383110
4 × 25 + 1 × 160.9/0.70.21.828.11,5570.727/1.15110140
4 × 35 + 1 × 160.9/0.70.21.929.61,9620.524/1.15135170
4 × 50 + 1 × 251/0.90.22.034.02,6010.387/0.727165200
4 × 70 + 1 × 351.1/0.90.52.240.33,9160.268/0.524210245
4 × 95 + 1 × 501.1/1.00.52.344.85,2600.193/0.387260300
4 × 120 + 1 × 701.2/1.10.52.650.26,5450.153/0.268305335
4 × 150 + 1 × 701.4/1.10.52.854.67,7800.124/0.268345380
4 × 185 + 1 × 951.6/1.10.52.960.59,6880.0991/0.193395430
4 × 240 + 1 × 1201.7/1.20.53.067.112,2530.0754/0.153465500
4 × 300 + 1 × 1501.8/1.40.53.273.715,0780.0601/0.124535565
3+2 Core
3 × 4 + 2 × 2.50.7/0.70.21.816.64124.61/7.4150
3 × 6 + 2 × 40.7/0.70.21.818.05253.08/4.6160
3 × 10 + 2 × 60.7/0.70.21.820.97141.83/3.086485
3 × 16 + 2 × 100.7/0.70.21.824.01,0161.15/1.8383110
3 × 25 + 2 × 160.9/0.70.21.828.11,4650.727/1.15110140
3 × 35 + 2 × 160.9/0.70.21.929.61,7690.524/1.15135170
3 × 50 + 2 × 251/0.90.22.034.02,3160.387/0.727165200
3 × 70 + 2 × 351.1/0.90.52.240.33,2300.268/0.524210245
3 × 95 + 2 × 501.1/1.00.52.344.84,7660.193/0.387260300
3 × 120 + 2 × 701.2/1.10.52.550.26,0800.153/0.268305335
3 × 150 + 2 × 701.4/1.10.52.654.67,0050.124/0.268345380
3 × 185 + 2 × 951.6/1.10.52.860.58,7670.0991/0.193395430
3 × 240 + 2 × 1201.7/1.20.53.067.111,1050.0754/0.153465500
3 × 300 + 2 × 1501.8/1.40.53.273.713,6450.0601/0.124535565

Packaging & Delivery

🪵

Export Wooden Drum

Fumigated solid wood or plywood. Standard for international shipping and container loading.

🔩

Iron-Wooden Drum

Reinforced composite drums for heavy armored cables (95 mm²+). Prevents drum deformation during transport.

📦

Custom Packaging

Customer-specified drum types, end caps, desiccant bags, custom drum marking and labeling.

Typical Applications

🏗️

Underground Distribution

Direct burial and cable ducts. Steel tape armor protects against ground pressure and sharp stones.

🏭

Industrial Plants

Heavy industrial environments with risk of mechanical impact from vehicles and falling objects.

Substations & Switchyards

Inter-station connections requiring physical protection. XLPE handles elevated ambient temperatures.

🏢

Commercial Buildings

Main feeders and risers where building codes specify armored cable for fire compartmentalization.

🏗️

Cable Trenches

Open trench and covered trench installations. Steel tape resists rodent damage and construction activity.

🌍

Utility Networks

Secondary distribution in public utility networks. Cost-effective PVC sheath for standard environmental conditions.

Request a Quote

Ready to Work Together? Build a project with us!
This field is required.
This field is required.
Learn More From

Frequently Asked Questions

As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.

Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.

Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.

For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.

Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.

inquiry@qiangligroup.com +86 153 3220 6813