Factory-Direct Supply of Certified Wires and Conductors for Diverse Industrial Applications
RVFAV-K Cable
Conductor: Copper, Class 5 flexible per EN 60228
Insulation: XLPE, rated 90°C
Armour: Double aluminium tape (non-magnetic)
Sheath: Flexible PVC, black, low halogen (Cl<15%)
Voltage: 0.6/1kV
Operating temperature: -40°C to +90°C
Package: Export wooden drum
Product Overview
RVFAV-K Cable is a 0.6/1kV single-core flexible power cable with XLPE insulation and aluminium tape armor. The name follows the Spanish/French designation system: R = flexible Class 5 conductor, V = XLPE insulation, FAV = aluminium tape armor (Facing Aluminum, V = PVC bedding), K = flexible for fixed installation. Unlike all previously described armored cables, RVFAV-K uses aluminium tape rather than steel — this is essential for single-core applications because a ferromagnetic steel armor would generate inductive eddy currents that cause dangerous overheating. The aluminium tape provides equivalent mechanical protection without the magnetic penalty. Additionally, the Class 5 finely stranded conductor gives RVFAV-K a minimum bending radius of only 5 × cable diameter, making it the most flexible armored cable in this product range.
Steel vs Aluminium Armour in Single-Core Cables
| Property | Steel Tape Armour (N2XBY, NYBY...) | Aluminium Tape Armour (RVFAV-K) |
|---|---|---|
| Magnetic Properties | Ferromagnetic — induces eddy currents in single-core | Non-magnetic — safe for single-core AC circuits |
| Conductor Temperature Rise from Armour | Significant in single-core applications | Minimal — no magnetic losses |
| Weight | Heavier | ~30% lighter |
| Mechanical Protection | Excellent — steel is harder | Good — adequate for underground and conduit protection |
| Corrosion Resistance | Requires galvanization | Inherently corrosion-resistant (aluminum oxide passivation) |
| Conductor Flexibility | Class 1 or 2 (solid/stranded) | Class 5 (finely stranded, R ≤5×D bend) |
Cable Construction

1. Conductor — Class 5 flexible copper, EN 60228
2. XLPE Insulation — 90°C rated, natural color
3. PVC Bedding — Black extruded separation sheath
4. Aluminium Tape Armour — Double layer, non-magnetic
5. PVC Outer Sheath — Flexible PVC, black, low halogen (Cl <15%)
Technical Characteristics
| Rated Voltage | 0.6/1kV |
| Max. Conductor Temperature | 90°C (continuous), 250°C (short-circuit, max 5s) |
| Min. Service Temperature | -40°C (fixed and protected installations) |
| Min. Bending Radius | 5 × D (most flexible armored cable available) |
| Fire Performance | Flame non-propagation EN 60332-1; CPR Eca per EN 50575 |
| Halogen Content | Low halogen — chlorine <15% |
| UV Resistance | UNE 211605 certified |
| Chemical & Oil Resistance | Good |
Standards & Certifications
| Standard | Scope |
|---|---|
| UNE 21123 | Spanish national standard — XLPE insulated, aluminium tape armored flexible cables 0.6/1kV. Primary standard for the RVFAV-K type. |
| HD 603 S1 | CENELEC Harmonization Document — base document for armored power cables in EU/EEA. |
| IEC 60502-1 | International standard — 90+ countries accept this certification. |
| EN 60228 | Conductor specification — Class 5 flexible conductors. |
| EN 60332-1 | Flame non-propagation — single cable vertical flame test. |
| EN 50575 | CPR (Construction Products Regulation) — Eca fire class. Mandatory for cables sold in EU. |
| UNE 211605 | Spanish standard — UV resistance certification for outdoor cables. |
Voltage Drop Characteristics
For the first time in this product series, voltage drop data (V/A·km) is provided directly in the specification table. Use this to calculate maximum circuit lengths: Max Length = (Permissible Voltage Drop × 1000) / (Vdrop × Current × cos φ). For precise project calculations, contact our engineering team.
Technical Specifications — Single Core Only
RVFAV-K is exclusively a single-core cable. For multi-core flexible armored applications, refer to RVFV-K. Current ratings: air 30°C, buried 20°C, 2.5 K·m/W. Voltage drop per IEC 60364-5-52 calculation method, 50Hz, cos φ = 0.8.
| Cross Section (mm²) | Outer Dia. (mm) | Weight (kg/km) | Current Air 30°C (A) | Current Buried 20°C (A) | Voltage Drop (V/A·km) |
|---|---|---|---|---|---|
| 1 × 16 | 14.4 | 370 | 101 | 79 | 2.55 |
| 1 × 25 | 16.0 | 485 | 135 | 101 | 1.61 |
| 1 × 35 | 17.1 | 595 | 169 | 122 | 1.16 |
| 1 × 50 | 18.6 | 730 | 207 | 144 | 0.86 |
| 1 × 70 | 20.3 | 960 | 268 | 178 | 0.594 |
| 1 × 95 | 22.4 | 1,255 | 328 | 211 | 0.428 |
| 1 × 120 | 24.4 | 1,510 | 383 | 240 | 0.339 |
| 1 × 150 | 26.3 | 1,810 | 444 | 271 | 0.275 |
| 1 × 185 | 28.3 | 2,215 | 510 | 304 | 0.220 |
| 1 × 240 | 31.3 | 2,805 | 607 | 351 | 0.167 |
| 1 × 300 | 34.0 | 3,420 | 703 | 396 | 0.133 |
Packaging & Delivery
Export Wooden Drum
Fumigated solid wood or plywood drums. Standard for single-core cable shipments. Flexible cable spools onto smaller drums.
Coil Packaging
Small cross-sections (≤50mm²) available in coils. Cost-efficient for short-haul transport and on-site handling.
Custom Packaging
Customer-specified drum types, custom marking, sequential meter marking. MOQ applies.
Typical Applications
RVFAV-K is specified for single-core flexible installations where ease of installation, tight bend radii, and non-magnetic armor are critical:
Single-Core Power Distribution
Individual phase conductors in 3-phase systems. Aluminium armor eliminates eddy current heating that steel-armored single-core cables suffer from.
Industrial Connections
Flexible connections to motors, generators, and transformers. Class 5 stranding permits easy routing in tight equipment spaces.
Underground Networks
Direct burial in LV distribution networks. Aluminium tape protects against soil pressure and rodent damage.
Outdoor Lighting
Underground feeders for street lighting, parking lot lighting, and outdoor area illumination. UV-stabilized sheath.
Cable Ducts & Conduits
Tight conduit pulls where 5×D bend radius allows installation in confined underground duct networks.
Cold Climate Installations
Rated to -40°C for fixed installations. Flexible PVC sheath remains pliable at sub-zero temperatures.
Request a Quote
Frequently Asked Questions
As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.
Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.
Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.
For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.
Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.