Factory-Direct Supply of Certified Wires and Conductors for Diverse Industrial Applications
RVFV-K Cable
Conductor: Copper, Class 5 flexible per EN 60228
Insulation: XLPE (V), rated 90°C
Armour: Double steel or aluminium tape
Sheath: Flexible PVC, black
Voltage: 600/1000V (0.6/1kV)
Number of cores: 1-core through 61-core (G-notation)
Package: Export wooden drum
Product Overview
RVFV-K Cable is a 0.6/1kV flexible armored power cable available in single-core through 61-core configurations. Naming: R = flexible Class 5 conductor, V = XLPE insulation, FV = tape armor (steel or aluminium), K = flexible for fixed installation. It is the general-purpose flexible armored cable — single-core versions use non-magnetic aluminium tape to prevent eddy current heating, while multi-core versions (both steel and aluminium tape are acceptable) since opposing magnetic fields from balanced phases cancel out. The Class 5 finely stranded conductor gives a bend radius of only 5 × D for single-core and 6-8 × D for multi-core — the most flexible armored cable family available in the 0.6/1kV range.
RVFAV-K vs RVFV-K
| Property | RVFAV-K | RVFV-K |
|---|---|---|
| Cores | Single-core only | 1-core through 61-core |
| Armour | Aluminium tape only | Steel or aluminium tape |
| Single-core armour rule | Always aluminium (non-magnetic) | Aluminium recommended for single-core; steel OK for multi-core |
| Voltage Drop Data | Yes | Yes |
| Standards | UNE 21123, HD 603 S1, IEC 60502-1 | Same |
Cable Construction

1. Conductor — Class 5 flexible copper, EN 60228
2. XLPE Insulation — 90°C rated
3. PVC Bedding — Separation sheath
4. Tape Armour — Steel or aluminium, double layer
5. PVC Outer Sheath — Flexible PVC, black
Flexible Copper Conductor
Class 5 finely stranded per EN 60228. Allows tight bend radii (5-8×D) impossible with Class 2 stranded cables.
XLPE Insulation (V)
Cross-linked polyethylene, 90°C continuous. XLPE chosen over PVC for higher current capacity in flexible armored cables.
PVC Bedding
Extruded PVC separation sheath between laid-up cores and armor. Provides smooth bedding surface and protects insulation.
Tape Armour (FV)
Double steel or aluminium tape, helically applied. Steel for multi-core (cost-effective, field-cancelling). Aluminium for single-core (non-magnetic).
Flexible PVC Sheath
Black flexible PVC. Maintains pliability at sub-zero temperatures while providing mechanical and chemical protection.
Installation Versatility
Open air, buried, in conduit. -5°C min installation, -40°C service. Meter-by-meter marking.
Technical Characteristics
| Rated Voltage | 600/1000V (0.6/1kV) |
| Max. Conductor Temperature | 90°C (continuous), 250°C (short-circuit) |
| Min. Bending Radius | 5-8 × D (varies by core count) |
| Installation Conditions | Open air, buried, in conduit |
| Fire Performance | EN 60332-1, CPR Eca per EN 50575 |
| Marking | Meter-by-meter sequential marking |
Applicable Standards
| Standard | Scope |
|---|---|
| UNE 21123 | Spanish national standard for XLPE insulated flexible armored cables 0.6/1kV. RVFV-K and RVFAV-K are defined under this standard. |
| HD 603 S1 | CENELEC Harmonization Document for distribution cables. |
| IEC 60502-1 | International standard — 90+ countries accept IEC 60502-1 certification. |
| EN 60228 | Conductor specification — Class 5 flexible conductor requirements. |
| EN 60332-1 | Flame non-propagation — single cable vertical flame test. |
| EN 50575 | CPR fire classification. RVFV-K achieves Eca class. |
Technical Specifications
All values per UNE 21123 / HD 603 S1. Current ratings: air 30°C, buried 20°C. Vdrop = V/A·km at 50Hz, cos φ = 0.8. "-" = not specified. For single-core applications, specify aluminium tape armor.
1-Core RVFV-K Cable
| Cross Section (mm²) | Outer Dia. (mm) | Weight (kg/km) | Current Air (A) | Current Buried (A) | Voltage Drop (V/A·km) |
|---|---|---|---|---|---|
| 1 × 16 | 14.4 | 370 | 101 | 79 | 2.55 |
| 1 × 25 | 16.0 | 485 | 135 | 101 | 1.61 |
| 1 × 35 | 17.1 | 595 | 169 | 122 | 1.16 |
| 1 × 50 | 18.6 | 730 | 207 | 144 | 0.86 |
| 1 × 70 | 20.3 | 960 | 268 | 178 | 0.594 |
| 1 × 95 | 22.4 | 1,255 | 328 | 211 | 0.428 |
| 1 × 120 | 24.4 | 1,510 | 383 | 240 | 0.339 |
| 1 × 150 | 26.3 | 1,810 | 444 | 271 | 0.275 |
| 1 × 185 | 28.3 | 2,215 | 510 | 304 | 0.220 |
| 1 × 240 | 31.3 | 2,805 | 607 | 351 | 0.167 |
| 1 × 300 | 34.0 | 3,420 | 703 | 396 | 0.133 |
2-Core through 4-Core RVFV-K Cable
| Cross Section (mm²) | Outer Dia. (mm) | Weight (kg/km) | Current Air (A) | Current Buried (A) | Voltage Drop (V/A·km) | |
|---|---|---|---|---|---|---|
| 2-Core | ||||||
| 2 × 1.5 | 12.3 | 225 | 26 | 26 | 31.0 | |
| 2 × 2.5 | 13.2 | 270 | 36 | 34 | 19.0 | |
| 2 × 4 | 14.1 | 320 | 49 | 44 | 11.8 | |
| 2 × 6 | 15.7 | 420 | 63 | 56 | 7.88 | |
| 2 × 10 | 17.1 | 530 | 86 | 73 | 4.68 | |
| 2 × 16 | 18.6 | 690 | 115 | 95 | 2.94 | |
| 3-Core | ||||||
| 3 × 1.5 | 12.8 | 255 | 23 | 22 | 26.8 | |
| 3 × 2.5 | 13.8 | 300 | 32 | 29 | 16.4 | |
| 3 × 4 | 15.1 | 380 | 42 | 37 | 10.2 | |
| 3 × 6 | 16.4 | 485 | 54 | 46 | 6.83 | |
| 3 × 10 | 17.8 | 630 | 75 | 61 | 4.06 | |
| 3 × 16 | 19.6 | 845 | 100 | 79 | 2.55 | |
| 3 × 25 | 23.9 | 1,270 | 127 | 101 | 1.61 | |
| 3 × 35 | 26.2 | 1,630 | 158 | 122 | 1.16 | |
| 3 × 50 | 29.8 | 2,105 | 192 | 144 | 0.86 | |
| 3 × 70 | 33.3 | 2,755 | 246 | 178 | 0.594 | |
| 3 × 95 | 40.1 | 3,960 | 298 | 211 | 0.428 | |
| 4-Core | ||||||
| 4 × 1.5 | 13.8 | 290 | 23 | 22 | 26.8 | |
| 4 × 2.5 | 14.7 | 350 | 32 | 29 | 16.4 | |
| 4 × 4 | 16.0 | 435 | 42 | 37 | 10.2 | |
| 4 × 6 | 17.4 | 540 | 54 | 46 | 6.83 | |
| 4 × 10 | 19.6 | 750 | 75 | 61 | 4.06 | |
| 4 × 16 | 21.8 | 1,020 | 100 | 79 | 2.55 | |
| 4 × 25 | 26.3 | 1,490 | 127 | 101 | 1.61 | |
| 4 × 35 | 29.1 | 1,965 | 158 | 122 | 1.16 | |
| 4 × 50 | 33.7 | 2,645 | 192 | 144 | 0.86 | |
| 4 × 70 | 39.4 | 3,910 | 246 | 178 | 0.594 | |
| 4 × 95 | 43.0 | 4,900 | 298 | 211 | 0.428 | |
3-Core + Reduced Neutral RVFV-K Cable
| Cross Section (mm²) | Outer Dia. (mm) | Weight (kg/km) | Current Air (A) | Current Buried (A) | Voltage Drop (V/A·km) |
|---|---|---|---|---|---|
| 3 × 16 + 1 × 10 | — | — | 100 | 79 | 2.55 |
| 3 × 25 + 1 × 16 | 25.0 | 1,355 | 127 | 101 | 1.61 |
| 3 × 35 + 1 × 16 | 27.3 | 1,695 | 158 | 122 | 1.16 |
| 3 × 50 + 1 × 25 | 31.5 | 2,315 | 192 | 144 | 0.86 |
| 3 × 70 + 1 × 35 | 36.0 | 3,120 | 246 | 178 | 0.594 |
| 3 × 95 + 1 × 50 | 41.6 | 4,425 | 298 | 211 | 0.428 |
| 3 × 120 + 1 × 70 | 46.8 | 5,895 | 346 | 240 | 0.339 |
| 3 × 150 + 1 × 70 | 51.5 | 7,005 | 399 | 271 | 0.275 |
| 3 × 185 + 1 × 95 | 56.5 | 8,730 | 456 | 304 | 0.220 |
| 3 × 240 + 1 × 120 | 63.4 | 11,040 | 538 | 351 | 0.167 |
| 3 × 300 + 1 × 150 | 70.2 | 12,905 | 621 | 396 | 0.133 |
5G through 61G (Multi-Core with Equal Earth) RVFV-K Cable
The G notation per UNE 21123 indicates all cores including earth are the same cross-section. Equal earth cross-section is mandatory under Spanish regulations for installations where the earth conductor may carry sustained fault currents.
| Core × Cross Section (mm²) | Outer Dia. (mm) | Weight (kg/km) | Current Air (A) | Current Buried (A) | Voltage Drop (V/A·km) | |
|---|---|---|---|---|---|---|
| 5G1.5 | 14.7 | 330 | 23 | 22 | 26.8 | |
| 5G2.5 | 15.7 | 400 | 32 | 29 | 16.4 | |
| 5G4 | 17.2 | 505 | 42 | 37 | 10.2 | |
| 5G6 | 18.7 | 630 | 54 | 46 | 6.83 | |
| 5G10 | 21.4 | 910 | 75 | 61 | 4.06 | |
| 5G16 | 24.1 | 1,255 | 100 | 79 | 2.55 | |
| 5G25 | 28.3 | 1,790 | 127 | 101 | 1.61 | |
| 5G35 | 31.5 | 2,355 | 158 | 122 | 1.16 | |
| 5G50 | 37.1 | 3,255 | 192 | 144 | 0.86 | |
| 5G70 | 42.5 | 4,725 | 246 | 178 | 0.594 | |
| 5G95 | 47.9 | 6,065 | 298 | 211 | 0.428 | |
| 5G120 | 53.5 | 7,580 | 346 | 240 | 0.339 | |
| 5G150 | 59.5 | 9,300 | 399 | 271 | 0.275 | |
| 6G1.5 | 14.3 | 325 | 26 | 26 | 33.9 | |
| 6G2.5 | 15.9 | 420 | 36 | 34 | 20.4 | |
| 6G4 | 17.5 | 540 | 49 | 44 | 11.9 | |
| 7G1.5 | 14.1 | 335 | 26 | 26 | 33.9 | |
| 7G2.5 | 15.6 | 430 | 36 | 34 | 20.4 | |
| 7G4 | 17.3 | 565 | 49 | 44 | 11.9 | |
| Industrial Multi-Core (10G through 61G) | ||||||
| 10G1.5 | 16.4 | 435 | 26 | 26 | 33.9 | |
| 10G2.5 | 17.7 | 555 | 36 | 34 | 20.4 | |
| 12G2.5 | 19.4 | 645 | 36 | 34 | 20.4 | |
| 12G4 | 22.4 | 880 | 49 | 44 | 11.9 | |
| 16G2.5 | 21.3 | 785 | 36 | 34 | 20.4 | |
| 19G2.5 | 22.5 | 890 | 36 | 34 | 20.4 | |
| 19G4 | 25.9 | 1,230 | 49 | 44 | 11.9 | |
| 24G2.5 | 24.5 | 1,045 | 36 | 34 | 20.4 | |
| 24G4 | 30.0 | 1,510 | 49 | 44 | 11.9 | |
| 37G1.5 | 25.9 | 1,065 | 26 | 26 | 33.9 | |
| 61G1.5 | 36.9 | 2,285 | 26 | 26 | 33.9 | |
Packaging & Delivery
Export Wooden Drum
Fumigated wooden drums. Standard for large cross-sections and export shipments.
Coil Packaging
Small cross-sections (≤35mm²) and multi-core (≥6G) available in coils. Cost-efficient for short-haul transport.
Custom Packaging
Customer-specified drums, custom marking, sequential meter marking. MOQ applies.
Typical Applications
Power Distribution
LV distribution in commercial and industrial installations. Flexible conductor enables easy routing through switchgear and panel boards.
Industrial Connections
Motor, generator, and transformer connections. Tight bend radius (5-8×D) allows installation in confined equipment enclosures.
Underground & Buried
Direct burial and underground ducts. Steel/aluminium tape provides mechanical protection against soil pressure and rodents.
Building Services
Main feeders and risers in multi-story buildings. Multi-core (≥10G) cables reduce the number of separate runs.
Control & Signal
Multi-core variants (12G, 19G, 24G, 37G, 61G) for combined power and control circuits in industrial automation.
Export & Spanish Markets
UNE 21123 certification for projects in Spain, Latin America, and Spanish-influenced markets. G-notation ensures local code compliance.
Request a Quote
Frequently Asked Questions
As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.
Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.
Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.
For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.
Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.