Power Cable

RVFV-K Cable

Flexible Power Cable 0.6/1kvV with Double Steel Tape Armoured

Conductor: Copper, Class 5 flexible per EN 60228
Insulation: XLPE (V), rated 90°C
Armour: Double steel or aluminium tape
Sheath: Flexible PVC, black
Voltage: 600/1000V (0.6/1kV)
Number of cores: 1-core through 61-core (G-notation)
Package: Export wooden drum

Product Overview

RVFV-K Cable is a 0.6/1kV flexible armored power cable available in single-core through 61-core configurations. Naming: R = flexible Class 5 conductor, V = XLPE insulation, FV = tape armor (steel or aluminium), K = flexible for fixed installation. It is the general-purpose flexible armored cable — single-core versions use non-magnetic aluminium tape to prevent eddy current heating, while multi-core versions (both steel and aluminium tape are acceptable) since opposing magnetic fields from balanced phases cancel out. The Class 5 finely stranded conductor gives a bend radius of only 5 × D for single-core and 6-8 × D for multi-core — the most flexible armored cable family available in the 0.6/1kV range.

RVFAV-K vs RVFV-K

PropertyRVFAV-KRVFV-K
CoresSingle-core only1-core through 61-core
ArmourAluminium tape onlySteel or aluminium tape
Single-core armour ruleAlways aluminium (non-magnetic)Aluminium recommended for single-core; steel OK for multi-core
Voltage Drop DataYesYes
StandardsUNE 21123, HD 603 S1, IEC 60502-1Same

Cable Construction

RVFV-K Cable Cross Section

1. Conductor — Class 5 flexible copper, EN 60228
2. XLPE Insulation — 90°C rated
3. PVC Bedding — Separation sheath
4. Tape Armour — Steel or aluminium, double layer
5. PVC Outer Sheath — Flexible PVC, black

1

Flexible Copper Conductor

Class 5 finely stranded per EN 60228. Allows tight bend radii (5-8×D) impossible with Class 2 stranded cables.

2

XLPE Insulation (V)

Cross-linked polyethylene, 90°C continuous. XLPE chosen over PVC for higher current capacity in flexible armored cables.

3

PVC Bedding

Extruded PVC separation sheath between laid-up cores and armor. Provides smooth bedding surface and protects insulation.

4

Tape Armour (FV)

Double steel or aluminium tape, helically applied. Steel for multi-core (cost-effective, field-cancelling). Aluminium for single-core (non-magnetic).

5

Flexible PVC Sheath

Black flexible PVC. Maintains pliability at sub-zero temperatures while providing mechanical and chemical protection.

6

Installation Versatility

Open air, buried, in conduit. -5°C min installation, -40°C service. Meter-by-meter marking.

Technical Characteristics

Rated Voltage600/1000V (0.6/1kV)
Max. Conductor Temperature90°C (continuous), 250°C (short-circuit)
Min. Bending Radius5-8 × D (varies by core count)
Installation ConditionsOpen air, buried, in conduit
Fire PerformanceEN 60332-1, CPR Eca per EN 50575
MarkingMeter-by-meter sequential marking

Applicable Standards

StandardScope
UNE 21123Spanish national standard for XLPE insulated flexible armored cables 0.6/1kV. RVFV-K and RVFAV-K are defined under this standard.
HD 603 S1CENELEC Harmonization Document for distribution cables.
IEC 60502-1International standard — 90+ countries accept IEC 60502-1 certification.
EN 60228Conductor specification — Class 5 flexible conductor requirements.
EN 60332-1Flame non-propagation — single cable vertical flame test.
EN 50575CPR fire classification. RVFV-K achieves Eca class.
G-notation explained: "5G16" = 5 cores of 16mm² each, all equal cross-section including the earth conductor. This is the Spanish/French convention (UNE 21123 / NF C 32-321) and differs from the German notation where the earth core is typically reduced. The G notation ensures the earth conductor has the same current-carrying capacity as the phase conductors, which is mandatory for certain installations under Spanish regulations.

Technical Specifications

All values per UNE 21123 / HD 603 S1. Current ratings: air 30°C, buried 20°C. Vdrop = V/A·km at 50Hz, cos φ = 0.8. "-" = not specified. For single-core applications, specify aluminium tape armor.

1-Core RVFV-K Cable

Cross Section
(mm²)
Outer Dia.
(mm)
Weight
(kg/km)
Current
Air (A)
Current
Buried (A)
Voltage Drop
(V/A·km)
1 × 1614.4370101792.55
1 × 2516.04851351011.61
1 × 3517.15951691221.16
1 × 5018.67302071440.86
1 × 7020.39602681780.594
1 × 9522.41,2553282110.428
1 × 12024.41,5103832400.339
1 × 15026.31,8104442710.275
1 × 18528.32,2155103040.220
1 × 24031.32,8056073510.167
1 × 30034.03,4207033960.133

2-Core through 4-Core RVFV-K Cable

Cross Section
(mm²)
Outer Dia.
(mm)
Weight
(kg/km)
Current
Air (A)
Current
Buried (A)
Voltage Drop
(V/A·km)
2-Core
2 × 1.512.3225262631.0
2 × 2.513.2270363419.0
2 × 414.1320494411.8
2 × 615.742063567.88
2 × 1017.153086734.68
2 × 1618.6690115952.94
3-Core
3 × 1.512.8255232226.8
3 × 2.513.8300322916.4
3 × 415.1380423710.2
3 × 616.448554466.83
3 × 1017.863075614.06
3 × 1619.6845100792.55
3 × 2523.91,2701271011.61
3 × 3526.21,6301581221.16
3 × 5029.82,1051921440.86
3 × 7033.32,7552461780.594
3 × 9540.13,9602982110.428
4-Core
4 × 1.513.8290232226.8
4 × 2.514.7350322916.4
4 × 416.0435423710.2
4 × 617.454054466.83
4 × 1019.675075614.06
4 × 1621.81,020100792.55
4 × 2526.31,4901271011.61
4 × 3529.11,9651581221.16
4 × 5033.72,6451921440.86
4 × 7039.43,9102461780.594
4 × 9543.04,9002982110.428

3-Core + Reduced Neutral RVFV-K Cable

Cross Section
(mm²)
Outer Dia.
(mm)
Weight
(kg/km)
Current
Air (A)
Current
Buried (A)
Voltage Drop
(V/A·km)
3 × 16 + 1 × 10100792.55
3 × 25 + 1 × 1625.01,3551271011.61
3 × 35 + 1 × 1627.31,6951581221.16
3 × 50 + 1 × 2531.52,3151921440.86
3 × 70 + 1 × 3536.03,1202461780.594
3 × 95 + 1 × 5041.64,4252982110.428
3 × 120 + 1 × 7046.85,8953462400.339
3 × 150 + 1 × 7051.57,0053992710.275
3 × 185 + 1 × 9556.58,7304563040.220
3 × 240 + 1 × 12063.411,0405383510.167
3 × 300 + 1 × 15070.212,9056213960.133

5G through 61G (Multi-Core with Equal Earth) RVFV-K Cable

The G notation per UNE 21123 indicates all cores including earth are the same cross-section. Equal earth cross-section is mandatory under Spanish regulations for installations where the earth conductor may carry sustained fault currents.

Core × Cross Section
(mm²)
Outer Dia.
(mm)
Weight
(kg/km)
Current
Air (A)
Current
Buried (A)
Voltage Drop
(V/A·km)
5G1.514.7330232226.8
5G2.515.7400322916.4
5G417.2505423710.2
5G618.763054466.83
5G1021.491075614.06
5G1624.11,255100792.55
5G2528.31,7901271011.61
5G3531.52,3551581221.16
5G5037.13,2551921440.86
5G7042.54,7252461780.594
5G9547.96,0652982110.428
5G12053.57,5803462400.339
5G15059.59,3003992710.275
6G1.514.3325262633.9
6G2.515.9420363420.4
6G417.5540494411.9
7G1.514.1335262633.9
7G2.515.6430363420.4
7G417.3565494411.9
Industrial Multi-Core (10G through 61G)
10G1.516.4435262633.9
10G2.517.7555363420.4
12G2.519.4645363420.4
12G422.4880494411.9
16G2.521.3785363420.4
19G2.522.5890363420.4
19G425.91,230494411.9
24G2.524.51,045363420.4
24G430.01,510494411.9
37G1.525.91,065262633.9
61G1.536.92,285262633.9
Multi-core derating: For cables with 6 or more cores, current ratings are per-core values assuming standard grouping. For installations with multiple cables in close proximity, apply additional derating factors per IEC 60364-5-52. Contact engineering for project-specific ampacity calculations.

Packaging & Delivery

🪵

Export Wooden Drum

Fumigated wooden drums. Standard for large cross-sections and export shipments.

📦

Coil Packaging

Small cross-sections (≤35mm²) and multi-core (≥6G) available in coils. Cost-efficient for short-haul transport.

📋

Custom Packaging

Customer-specified drums, custom marking, sequential meter marking. MOQ applies.

Typical Applications

Power Distribution

LV distribution in commercial and industrial installations. Flexible conductor enables easy routing through switchgear and panel boards.

🏭

Industrial Connections

Motor, generator, and transformer connections. Tight bend radius (5-8×D) allows installation in confined equipment enclosures.

🏗️

Underground & Buried

Direct burial and underground ducts. Steel/aluminium tape provides mechanical protection against soil pressure and rodents.

🏢

Building Services

Main feeders and risers in multi-story buildings. Multi-core (≥10G) cables reduce the number of separate runs.

🔌

Control & Signal

Multi-core variants (12G, 19G, 24G, 37G, 61G) for combined power and control circuits in industrial automation.

🌍

Export & Spanish Markets

UNE 21123 certification for projects in Spain, Latin America, and Spanish-influenced markets. G-notation ensures local code compliance.

Request a Quote

Ready to Work Together? Build a project with us!
This field is required.
This field is required.
Learn More From

Frequently Asked Questions

As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.

Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.

Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.

For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.

Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.

inquiry@qiangligroup.com +86 153 3220 6813