Factory-Direct Supply of Certified Wires and Conductors for Diverse Industrial Applications

Power Cable

Single Core 19/33KV Medium Voltage Unarmoured Cable

19/33kV XLPE Insulated Copper Tape Screened Unarmoured Power Cable

Voltage: 19/33kV (Um=36kV)
Conductor: Copper or aluminum, stranded Class 2
Conductor Screen: Extruded semi-conducting XLPE
Insulation: XLPE, 8.0mm nominal
Insulation Screen: Extruded semi-conducting XLPE
Metallic Screen: Copper tape, 16-35mm²
Outer Sheath: PVC or MDPE (LSZH per BS 7835)

Product Overview

Single Core 19/33kV (Um=36kV) Medium Voltage Unarmoured Cable is an XLPE-insulated, copper tape screened power cable designed for primary distribution networks at the highest commercially common medium voltage level. 19/33kV is the interface voltage between distribution and sub-transmission — above standard MV distribution (6.35/11kV, 8.7/15kV) but below high-voltage transmission (66kV, 132kV). This cable is the standard workhorse for wind farm collector grids, solar farm MV networks, industrial plant ring mains, and utility distribution substation interconnections where the power density or distance demands a voltage step above the 11-15kV class.

19/33kV: Where This Voltage Class Is Used

19/33kV is the dominant MV collection voltage in renewable energy and primary distribution. It is NOT a general building services cable, but a utility-grade product for projects where hundreds of amperes must be moved over kilometres with acceptable voltage drop. Key deployment scenarios: (1) Wind farm 33kV collector circuits connecting turbine transformers to the on-site substation; (2) Solar farm MV collection network; (3) Utility 33kV distribution ring mains feeding 33/11kV primary substations; (4) Large industrial plants (steel mills, chemical plants, mining operations) with private MV networks; (5) Data centre campus MV distribution.

MV Cable Construction vs LV Cable Construction

Medium voltage cables are fundamentally different from low voltage (0.6/1kV) cables. The addition of semi-conducting layers and a metallic screen is not optional — it is an electrical requirement driven by the physics of high electrical field stress at MV levels:

LayerLV Cable (0.6/1kV)MV Cable (19/33kV)Purpose at MV
Conductor ScreenNot requiredExtruded semi-conducting XLPESmooths the conductor surface to eliminate electrical field concentrations that cause partial discharge
Insulation Thickness0.7-2.4mm8.0mmWithstands 19kV phase-to-ground continuous, 33kV phase-to-phase, 36kV maximum system voltage
Insulation ScreenNot requiredExtruded semi-conducting XLPEProvides a smooth equipotential boundary at the insulation surface; essential for partial discharge-free operation
Metallic ScreenNot requiredCopper tape, 16-35mm²Carries earth fault current, provides a defined earth path, and acts as a moisture barrier; screen cross-section calculated per system fault level

Cable Construction

MV Single Core 19/33kV Cable Cross Section

1. Conductor — Copper or aluminium, stranded Class 2
2. Conductor Screen — Extruded semi-conducting XLPE
3. XLPE Insulation — 8.0mm nominal, 90°C rated
4. Insulation Screen — Extruded semi-conducting XLPE, fully bonded
5. Metallic Screen — Copper tape, 16-35mm²
6. Separation Sheath — PVC bedding layer
7. Outer Sheath — PVC or MDPE (LSZH option)

1

Conductor

Copper: stranded Class 2. Aluminium: solid or stranded Class 2. Compacted circular for reduced OD and smooth screening surface.

2

Conductor Screen

Extruded semi-conducting XLPE compound, fully bonded to insulation. Eliminates air gaps at the conductor-insulation interface — the primary source of partial discharge in MV cables.

3

XLPE Insulation

8.0mm for all cross-sections. Dry-cured, triple-extruded with screens (CDCC process). Tested to 2.5U₀ for partial discharge: no detectable PD above 5 pC at 1.73U₀ per IEC 60840.

4

Insulation Screen

Extruded semi-conducting XLPE, fully bonded and strippable. Provides smooth equipotential boundary. Prevents electrical tree growth at insulation-sheath interface.

5

Metallic Screen

Copper tape applied over the insulation screen. Cross-section (16/25/35mm²) dimensioned per system earth fault level and duration. Also functions as longitudinal water barrier.

6

Separation Sheath + Outer Sheath

Extruded PVC bedding + PVC or MDPE outer sheath. LSZH available per BS 7835. Black, UV-stabilised for outdoor and direct-burial applications.

Technical Characteristics

Rated Voltage U₀/U (Um)19/33kV (36kV maximum system voltage)
Max. Conductor Temperature90°C (continuous), 250°C (short-circuit, max 5s)
Min. Bending Radius12 × overall diameter
Frequency50Hz
Conductor TypesCopper (stranded Class 2), Aluminium (solid or stranded Class 2)
Sheath OptionsPVC, MDPE, or LSZH (BS 7835)
Partial Discharge Test<5 pC at 1.73U₀ (per IEC 60840)
Test Voltage (AC)2.5U₀, 30 minutes

Applicable Standards

StandardScope
BS 6622British standard for XLPE insulated cables with rated voltages 3.8/6.6kV to 19/33kV. Covers single-core and 3-core unarmoured and armoured cables.
IEC 60502-2International standard for power cables with extruded insulation, rated 6kV to 30kV. The global reference document for MV cable design and testing.
IEC 60840Power cables with extruded insulation for rated voltages above 30kV up to 150kV — test methods and requirements. Referenced for partial discharge testing at 19/33kV.
BS 7835British standard for LSZH sheathed MV cables for use in public buildings and areas where fire safety requires halogen-free materials.
IEC 60228Conductor specification — Class 2 stranded for copper and aluminium MV conductors.
IEC 60332-1Flame non-propagation test for single cable.
Partial discharge (PD) is the critical quality parameter for MV cables. Unlike LV cables where simple insulation resistance is sufficient, MV cable quality is defined by its PD performance. Every cable drum we ship includes a partial discharge test certificate showing <5 pC at 1.73U₀ — the industry-accepted maximum for reliable 30+ year service life. Cables that pass standard voltage tests but exhibit elevated PD levels will fail prematurely in service due to progressive insulation degradation.

Technical Specifications — Single Core 19/33kV

XLPE insulation: 8.0mm (all cross-sections). Copper wire screen area: 16mm² (50-120mm²), 25mm² (150-300mm²), 35mm² (400-630mm²). Aluminium conductor: solid (up to 300mm²) or stranded Class 2.

Cross Section
(mm²)
Insulation
(mm)
Cu Screen
(mm²)
Sheath
(mm)
Outer Dia.
(mm)
Weight Cu
(kg/km)
Weight Al
(kg/km)
1 × 508.0162.034.21,5801,270
1 × 708.0162.035.81,8201,380
1 × 958.0162.137.62,1201,510
1 × 1208.0162.139.02,4001,630
1 × 1508.0252.240.92,7401,810
1 × 1858.0252.242.43,1101,950
1 × 2408.0252.345.13,7202,180
1 × 3008.0252.447.34,3502,460
1 × 4008.0352.551.25,4102,880
1 × 5008.0352.653.86,4203,320
1 × 6308.0352.759.07,8003,780
Copper screen dimensioning: The metallic screen cross-section is selected based on the maximum single-phase-to-earth fault current and its duration in the system where the cable is installed. The values above (16, 25, 35mm²) are standard IEC 60502-2 recommendations. For systems with unusually high earth fault levels, a larger screen cross-section may be required — contact engineering with your system fault study data for confirmation.

Packaging & Delivery

MV cables require special handling. XLPE insulation is sensitive to moisture ingress during storage — all cable ends are sealed with heat-shrink end caps and desiccant bags at the factory. Drums must be stored with ends sealed until termination.

🪵

Export Wooden Drum

Fumigated wooden drums. 19/33kV cables are heavy — minimum drum flange diameter 20× cable OD. Heat-shrink end caps included.

🛡️

Moisture Protection

Cable ends factory-sealed with dual-layer heat-shrink caps and silica gel. Drums wrapped in UV-resistant polyethylene for outdoor storage.

📋

Documentation Package

Partial discharge test certificate, routine test report, material traceability documentation, and drum inspection checklist per BS 6622.

Typical Applications — 19/33kV Voltage Class

🌬️

Wind Farm Collector Grids

33kV is the universal wind farm MV collection voltage. Each turbine transformer (typically 0.69/33kV) feeds into a 33kV collector circuit of 3-8 turbines running to the on-site substation.

☀️

Solar Farm MV Collection

Large-scale PV installations (50MW+) aggregating inverter output at 33kV for step-up to grid connection voltage at the point of interconnection.

Utility 33kV Distribution

Primary distribution ring mains in urban and industrial areas. 33/11kV primary substations are the backbone of most national distribution networks.

🏭

Heavy Industrial MV Networks

Steel mills, chemical plants, cement factories, and mining operations with private 33kV ring mains for motor loads above 1MW.

💻

Data Centre MV Distribution

33kV campus ring feeding multiple 33/0.4kV substations at hyperscale data centres. MV distribution reduces current and cable size vs 11kV.

🔄

Substation Interconnection

19/33kV cables between GIS switchgear bays in primary substations. Unarmoured construction suitable for protected cable trenches and ducts.

Request a Quote

Ready to Work Together? Build a project with us!
This field is required.
This field is required.
Learn More From

Frequently Asked Questions

As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.

Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.

Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.

For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.

Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.

inquiry@qiangligroup.com +86 153 3220 6813