Aerial Bundled Cable

URD Cable Single Conductor Aluminum Underground Direct Burial Cable 600V

600V Single Conductor URD Aluminum XLPE Underground Direct Burial Cable
Voltage: 600V, 130°C emergency overload (100h/12 months)
Conductor: 1350-H19 or AA-8000 aluminium, Class B compressed
Insulation: Black XLPE, 60/80/95/110 mils by size tier
Rating: 90°C dry/wet/burial, UL Listed USE-2
Range: AWG 8 to 1000 kcmil, 19 code-name variants
Ampacity: Full NEC (60/75/90°C) + ICEA (buried + conduit)
Standard: ICEA S-105-692, UL 854, RUS accepted

Product Overview

Single Conductor URD Cable is a 600V XLPE-insulated individual underground residential distribution conductor with aluminium core, manufactured to ICEA S-105-692 and UL 854 as UL Listed USE-2, RUS accepted. Conductors are Class B compressed concentric lay stranded 1350-H19 or AA-8000 aluminium alloy per ASTM B231 / B800 / B801. Phase conductors are black XLPE; neutral conductors are black XLPE with yellow striping or full yellow jacket. Rated 90°C continuous dry/wet/direct burial, with 130°C emergency overload capability (max 100 hours per 12 consecutive months). Single conductor URD is the building block of all URD assemblies — individual phase and neutral conductors used separately in ducts, raceways, or direct burial for street lighting circuits, transformer risers, and custom field-cabled configurations. With 19 code-name variants from AWG 8 (Cornell) to 1000 kcmil (Fordham), this is the most comprehensive URD range available.

1

Aluminium 1350 / AA-8000

Class B compressed concentric lay. 1350-H19 or AA-8000 alloy. 7-strand (≤AWG 2), 19-strand (AWG 1-4/0), 37-strand (250-500 kcmil), 61-strand (600-1000 kcmil).

2

XLPE Insulation (USE-2)

Black thermoset XLPE. 90°C continuous, 130°C emergency overload. Insulation: 60 mils (≤AWG 2), 80 mils (AWG 1-4/0), 95 mils (250-500), 110 mils (600-1000).

3

Single Conductor

Individual conductors — no cabling. Build custom Duplex/Triplex/Quadruplex assemblies in the field, or use individually for street lighting and riser circuits.

4

600V Secondary + 130°C Overload

Rated 600V. 130°C emergency overload (100h/12 months) — higher than the standard 90°C USE-2 rating for contingency operation during network faults.

5

19 Code Names (8AWG–1000kcmil)

Comprehensive range: Cornell → Fordham. Dual-unit table with imperial (in/lb) + metric (mm/kg). Full NEC + ICEA ampacity data.

6

UL / RUS Certified

UL Listed USE-2 per UL 854 and NEC 310.104(A). RUS accepted. ICEA S-105-692 compliant for all utility underground applications.

Technical Characteristics

Rated Voltage600V (secondary distribution and USE-2 applications)
Normal Operation Temperature90°C (dry, wet, and direct burial)
Emergency Overload Temperature130°C (max 100 hours within 12 consecutive months)
Conductor Material1350-H19 or AA-8000 aluminium alloy, Class B compressed
InsulationBlack thermoset XLPE — 60/80/95/110 mils by size
Neutral IdentificationBlack XLPE with yellow striping or full yellow jacket
ListingUL Listed USE-2 per UL 854, RUS accepted, ICEA S-105-692

Applicable Standards

StandardScope
ICEA S-105-692600V single layer thermoset insulated utility underground distribution cable. Primary standard for all URD conductor construction and testing.
UL 854Service Entrance Cables. USE-2 listing per NEC 310.104(A) for underground service entrance in all environmental conditions.
ASTM B231 / B800 / B801Conductor material standards: B231 (1350 concentric lay), B800 (AA-8000 series alloy), B801 (AA-8000 concentric lay stranded).
ICEA P-53-426Ampacity tables for single conductor URD — direct buried and pole riser conduit. Referenced for all ICEA ampacity values in this specification.
RUS AcceptedUSDA Rural Utilities Service. Required for federally funded rural electric distribution infrastructure projects.

URD Family — Complete Comparison

TypeConductorsServiceCode Names
Single Conductor URD1 × phase or neutralIndividual runs, street lighting, custom assembliesCornell → Fordham (19)
Duplex URD1 × phase + 1 × neutral120V two-wire, street lighting circuitsBard → Everett (4)
Triplex URD2 × phase + 1 × neutral120/240V split-phase residentialErskine → Fairfield (15)
Quadruplex URD3 × phase + 1 × neutral208Y/120V three-phase commercialTulsa → Windham (15)

Technical Specifications

All data per ICEA S-105-692. 19 code-name variants from AWG 8 to 1000 kcmil. Insulation thickness increases in four tiers: 60 mils (≤AWG 2), 80 mils (AWG 1–4/0), 95 mils (250–500 kcmil), 110 mils (600–1000 kcmil). NEC ampacity per Table 310.16 (≤3 conductors, 30°C ambient). ICEA ampacity per P-53-426 (1 circuit, 100% load factor).

Code
Name
Size
(AWG/kcmil)
Strand-
ing
Insul.
(in)
Insul.
(mm)
Nom. Dia.
(in)
Nom. Dia.
(mm)
Weight
(lb/kft)
Weight
(kg/km)
NEC
60°C
NEC
75°C
NEC
90°C
ICEA
Buried
ICEA
Conduit
Cornell870.061.520.266.634514044497436
Princeton670.061.520.307.647704656599647
Mercer470.061.520.358.96710063728111760
Clemson270.061.520.4110.4971448610010815482
Kenyon1190.082.030.4912.41281909811112417197
Harvard1/0190.082.030.5213.2154229115133146193112
Yale2/0190.082.030.5714.5186277132150162221132
Tufts3/0190.082.030.6215.7225335150172189253155
Beloit4/0190.082.030.6817.3274408173200221290185
Hofstra250370.0952.410.7519.1329490196228248317199
Gonzaga300370.0952.410.8120.6385573224255281349223
Rutgers350370.0952.410.8521.6439653242278302381248
Dartmouth400370.0952.410.9022.9493734259300329410272
Brown450370.0952.410.9423.9547814439295
Emory500370.0952.410.9824.9601894299344378464318
Duke600610.112.791.0927.77251,079328377416514355
Furman700610.112.791.1629.58301,235362416459549386
Sewanee750610.112.791.1930.28831,314368427470567403
Fordham1000610.112.791.3434.01,1441,702431494540665492
Ampacity notes: NEC values per NEC Table 310.16 (≤3 current-carrying conductors, 30°C ambient). 60°C/75°C/90°C columns correspond to termination temperature ratings. Brown (450 kcmil) has no NEC values on the reference page (—). ICEA Direct Buried: 1 circuit, 100% load factor, earth RHO 90, 25°C ambient. ICEA Pole Riser Conduit: 1 circuit, 100% load factor, 40°C ambient, 1 cable/duct. All ICEA values per ICEA P-53-426. Single conductor URD has the highest ampacity per cross-section vs cabled assemblies — no mutual heating. 130°C emergency overload rating: max 100 hours within 12 consecutive months.

Packaging & Delivery

ParameterStandard
Drum TypeExport wooden drum / iron-wooden drum / as per customer requirement
Length per DrumStandard reels per AWG/kcmil; custom cut lengths on request
Drum MarkingManufacturer, URD Single, code name, voltage, AWG, insulation, length, weight, drum number, UL/RUS marks
Cable End SealingHeat-shrink end caps to prevent moisture ingress
Outer ProtectionWeatherproof wrapping for sea freight
Delivery ConditionFactory-new, tested per ICEA S-105-692 / UL 854, UL Listed USE-2

Typical Applications

Single conductor URD is the most flexible URD product — individual phase and neutral conductors for custom field-cabled assemblies, street lighting circuits, transformer risers, and any underground secondary application where a factory-cabled Duplex/Triplex/Quadruplex is not the right tool:

💡

Street Lighting Circuits

Individual 600V conductors for underground street lighting loops. Field-cable with neutral for custom circuit configurations.

Transformer Riser Poles

Pole riser conduit from underground secondary to pad-mount or pole-mount transformer. High ICEA conduit ampacity rating.

🔧

Custom Field Assemblies

Build Duplex/Triplex/Quadruplex in the field for non-standard AWG combinations not covered by factory code names.

🌱

Direct Burial

Rated for direct earth burial without conduit. 90°C continuous, 130°C emergency overload for contingency operation.

🇺🇸

US Utility Networks

ICEA S-105-692 + RUS accepted. UL Listed USE-2 per NEC 310.104(A) for all US utility underground secondary applications.

🏗️

Duct & Raceway

Suitable for installation in underground electrical ducts and raceways. Highest ampacity per cross-section — no mutual heating from adjacent conductors.

Request a Quote

Ready to Work Together? Build a project with us!
This field is required.
This field is required.
Learn More From

Frequently Asked Questions

As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.

Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.

Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.

For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.

Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.

inquiry@qiangligroup.com +86 153 3220 6813