Factory-Direct Supply of Certified Wires and Conductors for Diverse Industrial Applications
H07Z-R Halogen Free Flame Retardant Building Wire
Voltage: 450/750V, test 2,500V, CE LVD + ROHS
Conductor: Class 2 stranded bare copper, VDE-0295 / IEC 60228, 7-strand concentric lay
Insulation: LSOH cross-link polyolefin EI5 (thermosetting), 90°C, -40°C static
Bending: 8×D (flexing & static), 10 MΩ·km insulation resistance
Range: 15 sizes 1.5-240mm², 21-2,371 kg/km, 100m/roll
Fire Safety: Zero halogen — IEC 60754-2 / EN 50267 + EN 50268 smoke density
Standard: HD 22.9 S2, VDE-0282 Part-9, BS 7211, CE, ROHS
Product Overview
H07Z-R Halogen Free Flame Retardant Building Wire is a single-core Class 2 stranded copper conductor LSOH building wire manufactured to HD 22.9 S2, VDE-0282 Part-9, and BS 7211. The -R suffix designates rigid stranded construction (7-strand concentric lay, Class 2 per VDE-0295 / IEC 60228) as opposed to the -K flexible Class 5 variant. LSOH cross-link polyolefin EI5 thermosetting insulation delivers zero halogen acid gas emission, low smoke density, and self-extinguishing combustion properties — the standard safety wire for all European public buildings, hospitals, and enclosed spaces where toxic PVC smoke would threaten life and electronic equipment. Rated 450/750V with 90°C continuous temperature, -40°C static rating, and 10 MΩ·km insulation resistance — the same fire-safety and electrical performance as H07Z-K, but with the cost and installation advantages of Class 2 stranding for straight conduit and trunking runs.
The -R variant occupies an important niche in LSOH building wiring: where H07Z-K (Class 5 flexible) is specified for panel interiors and appliance wiring that requires extreme flexibility through tight routing paths, H07Z-R (Class 2 stranded) is the general-purpose LSOH wire for conduit pulls, trunking, and straight equipment connections — the LSOH equivalent of the workhorse H07V-R PVC wire. The 7-strand concentric lay is less expensive to manufacture than Class 5's fine multi-strand construction (fewer wire-drawing operations, simpler stranding), and the more rigid cable holds its shape better in vertical risers and long cable tray spans — an installation advantage in commercial and industrial LSOH projects where the wire is pulled once and remains stationary for decades. The bending radius (8×D) is the same as H07Z-K — determined by the polyolefin insulation, not the conductor stranding class. The insulation wall thickness and overall diameter are also identical between -R and -K for the same cross-section, making the two variants dimensionally interchangeable in the same conduit.
Fifteen sizes from 1.5mm² to 240mm² cover the full European building wiring range, all at 100m per roll in export wooden case packaging. The CE marking under the Low Voltage Directives and ROHS compliance ensure barrier-free market access across all CENELEC member states and the United Kingdom. H07Z-R completes the LSOH building wire trilogy alongside H07Z-K (flexible) and HFIX (Korean standard) — a family of halogen-free single-core wires covering every stranding class, voltage class, and regulatory framework in the global LSOH market.

Bare copper conductor — 7-strand orange copper, Class 2 concentric lay per VDE-0295 / IEC 60228
LSOH cross-link polyolefin insulation — Dark blue thermosetting ring, zero halogen, EI5 type per BS EN 50363-5
Class 2 Stranded Copper
Fine bare copper strands to VDE-0295 Class 2, IEC 60228. 7-strand concentric lay — cost-effective general-purpose LSOH wire for conduit and trunking runs.
LSOH Cross-Link Polyolefin EI5
Thermosetting insulation per BS EN 50363-5. 90°C, -40°C static, zero halogen, 10 MΩ·km. Self-extinguishing — LOI exceeds atmospheric oxygen concentration.
-R vs -K: Rigid vs Flexible
H07Z-R (Class 2, 7-strand) for straight conduit pulls. H07Z-K (Class 5, fine strand) for panel interiors. Same voltage, same LSOH chemistry — different stranding.
8×D Bending, -40°C Static
Same bending radius as H07Z-K — LSOH stiffness is insulation-limited, not conductor-limited. -40°C rating enables cold-climate outdoor and unheated installations.
15 Sizes 1.5-240mm²
1.5mm² (21 kg/km) to 240mm² (2,371 kg/km). 100m/roll. Standard LSOH building wire range — no micro-gauge 0.5-1.0mm² sizes (those are -K only).
9 Standards + CE + ROHS
HD 22.9 S2 + VDE-0282 Part 9 + BS 7211 + IEC 60754-2 + EN 50267 + CE LVD + ROHS. Full EU/UK regulatory compliance suite.
Technical Characteristics
| Working Voltage | 450/750V |
| Test Voltage | 2,500V |
| Flexing Bending Radius | 8 × outer diameter |
| Static Bending Radius | 8 × outer diameter |
| Flexing Temperature | -15°C to +90°C |
| Static Temperature | -40°C to +90°C |
| Insulation Resistance | 10 MΩ × km (minimum) |
| Flame Retardant | IEC 60332.1 / EN 50265-2-1 |
Applicable Standards
| Standard | Scope |
|---|---|
| HD 22.9 S2 | CENELEC harmonised document for halogen-free cross-link polyolefin insulated cables. Primary European standard for H07Z-R (Class 2 stranded variant). |
| VDE-0282 Part-9 | German national adoption of HD 22.9. VDE mark required for German and Austrian LSOH installations. |
| BS 7211 | British Standard for thermosetting insulated cables — covers H07Z-R for UK market under BS 7671 wiring regulations. |
| IEC 60754-2 / EN 50267 | Halogen acid gas emission — zero HCl/HF/HBr certified per IEC and CENELEC test methods. |
| CE LVD 73/23/EEC & 93/68/EEC | CE marking under European Low Voltage Directives — mandatory for sale in all EU/EEA member states. |
LSOH Wire Trilogy — Complete Strangding Spectrum
| Type | Standard | Class | Range | Bending | Use Case |
|---|---|---|---|---|---|
| H07Z-R | HD 22.9 S2 / BS 7211 | Class 2 (7-strand) | 1.5-240mm² | 8×D | Conduit & trunking — general purpose LSOH |
| H07Z-K / H05Z-K | HD 22.9 S2 / BS 7211 | Class 5 (flexible) | 0.5-240mm² | 8×D | Panel interiors — flexible routing LSOH |
| HFIX | KS C 3341 | Class 1 & 2 | 1.5-300mm² | 4×D | Korean LSOH — solid & stranded dual |
Technical Specifications
Class 2 stranded bare copper per VDE-0295 / IEC 60228. LSOH cross-link polyolefin EI5 thermosetting insulation per BS EN 50363-5. Nominal copper weight = conductor only. Nominal weight = conductor + insulation. All sizes single core, 100m/roll.
| Cross Section (No. × mm²) | Insulation (mm) | Overall Dia. (mm) | Copper Weight (kg/km) | Total Weight (kg/km) |
|---|---|---|---|---|
| Standard Insulation — 1.5-10mm² | ||||
| 1 × 1.5 | 0.7 | 3.0 | 14.4 | 21 |
| 1 × 2.5 | 0.8 | 3.6 | 24 | 33 |
| 1 × 4 | 0.8 | 4.1 | 39 | 49 |
| 1 × 6 | 0.8 | 4.7 | 58 | 71 |
| 1 × 10 | 1.0 | 6.0 | 96 | 114 |
| Heavy Insulation — 16-240mm² | ||||
| 1 × 16 | 1.0 | 6.8 | 154 | 172 |
| 1 × 25 | 1.2 | 8.4 | 240 | 265 |
| 1 × 35 | 1.2 | 9.3 | 336 | 360 |
| 1 × 50 | 1.4 | 10.9 | 480 | 487* |
| 1 × 70 | 1.4 | 12.6 | 672 | 683 |
| 1 × 95 | 1.6 | 14.7 | 912 | 946 |
| 1 × 120 | 1.6 | 16.0 | 1,152 | 1,174 |
| 1 × 150 | 1.8 | 17.9 | 1,440 | 1,448 |
| 1 × 185 | 2.0 | 20.0 | 1,776 | 1,820 |
| 1 × 240 | 2.2 | 22.7 | 2,304 | 2,371 |
Packaging & Delivery
| Parameter | Standard |
|---|---|
| Package | 100m per roll, export wooden case & pallet |
| Roll Marking | Manufacturer, H07Z-R, 450/750V, LSOH, cross-section, length, weight, batch, HAR/CE/VDE/BS/ROHS marks |
| Colour Options | Standard LSOH identification colours (typically black, with colour on request) |
| Outer Protection | Wooden case — standardised across all LSOH product lines; ROHS compliant packaging materials |
| Delivery Condition | Factory-new, tested per HD 22.9 S2 / BS 7211, LSOH certified per IEC 60754-2 / EN 50267, CE + ROHS |
Typical Applications
H07Z-R is the Class 2 stranded workhorse of the LSOH building wire family — specified for conduit and trunking runs in European public buildings where H07Z-K's extreme flexibility is unnecessary and H07Z-R's cost advantage is welcomed:
Public & Government Buildings
Standard LSOH conduit and trunking wire for European public buildings — the -R cost advantage over -K matters on large-scale government projects by the kilometre.
Hospital Power Circuits
Branch circuit wiring from distribution boards to bedhead trunking. Class 2 stranded pulls through riser conduit smoothly, holds position in vertical drops.
Commercial Building Riser Wiring
LSOH riser circuits in commercial buildings — the stiffer Class 2 construction resists sagging in long vertical runs better than Class 5 flexible wire.
Equipment Internal Wiring
Internal wiring of appliances and equipment up to 450/750V where 90°C rating and zero halogen emission are required per EU tender specifications.
EU / CENELEC Public Works
CE + ROHS + VDE + BS quadra-certified. Accepted in all EU/EEA public building tender documents that mandate LSOH wire for enclosed spaces.
Cold Storage & Outdoor
-40°C static rating — installs in unheated warehouses, cold storage facilities, and outdoor cabinets where PVC would embrittle during winter pulling.
Related Products
Complete your LSOH and building wire range — European, Korean, and international standards:
450/750V Korean LSOH building wire — KS C 3341, 90°C, 20 colours, Class 1 & 2, 1.5-300mm²
450/750V single-core solid & stranded PVC indoor wire — GB/T 5023, BS 6004, up to 630mm²
300/500V copper PVC/PVC multi-core building cable — VDE 0250, 1-5 core, damp/wet rated
Request a Quote
Frequently Asked Questions
As a factory, we offer flexible MOQ depending on the cable type. For standard stock items, MOQ is low; for customized specifications, please contact our sales team for a detailed quote.
Yes, Qiangli cables are manufactured in compliance with international standards such as UL, CE, TUV, and VDE. We provide full test reports and certificates upon request.
Absolutely. We have a dedicated R&D team that can customize cable structure, material, color, and printing to meet your specific project needs.
For standard products, lead time is usually 7-15 days. For large-scale project orders or customized products, it typically ranges from 20 to 30 days.
Yes, we provide free samples for most standard cables. You only need to cover the international courier costs. Contact us to arrange your sample shipment.
